Honeywell Q539F User Manual

Page 8

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

PROTECTION AS REQUIRED.

És

^JUMPER FOR AUTO FAN IN ELECTRIC HEAT APPLICATIONS. IF

JUMPER IS USED. MEASURE COMBINED “HEAT RELAY" AND
"FAN RELAY" CURRENT RATINGS.

A

3\ RECOMMENDED HEAT ANTICIPATOR SETTING IS THE COMBINED

CURRENT DRAW OF THE FAN RELAY AND HEAT RELAY AS THE FAN
RELAY CURRENT PASSES THROUGH THE HEAT ANTICIPATOR.

M2162

SWITCH

HEATING

COOLING

RELAY OR

CON-

VALVE

TACTOR

I______________________

FAN
RELAY

EXTERNAL
SWITCHING
FOR
AUTO FAN

Fig. 9—Q539G IN HEATING APPLICATION

AUTOMATIC FAN OPERATION.

WITH

A X TERMINAL IS USED ON 0539 MODELS WITH FACTORY-!NSTAUED

INDICATOR LED.

A POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

Fig. 10—Q539H IN HEATING-COOLING APPLICATION

AND

AUTOMATIC

FAN

OPERATION

SWITCHING.

A

A

^1\ X TERMINAL IS USED ON Q539 MODELS WITH FACTORY-INSTALLED

INDICATOR LED.

A

WITH NO O TERMINAL LOAD. THERMOSTAT CURRENT DURING HEATING

CYCLE VARIES DEPENDING ON WHETHER FAN SWITCH IS IN THE ON OR

AUTO POSITION. HEATER SHOULD BE SET FOR COMBINED CURRENT

LEVEL OF HEAT RELAY AND FAN RELAY COILS. WITH O TERMINAL

LOAD. SET THERMOSTAT HEAT ANTICIPATOR TO ITS MAXIMUM

SETTING AS COOLING ANTICIPATOR IN SERIES WITH 0 TERMINAL

LOAD PROVIDES HEAT ANTICIPATION IN THE HEATING CYCLE. (LIMIT

THE THERMOSTAT HEATING LOAD CURRENT TO 0.8 AMPS TO ASSURE

GOOD PERFORMANCE.)

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

Fig. 11—Q539J IN HEATING-COOLING APPLICATION WITH AUTO FAN OPERATION.