Stardance direct vent/natural vent gas heater – Vermont Casting SDDVT User Manual

Page 22

Advertising
background image

22

Stardance Direct Vent/Natural Vent Gas Heater

20012734

Supporting DIRECT-TEMP: Vertical Support
Vertical installations can be supported by two methods:
Ceiling Support (CS) (used in flat ceiling installation)
comes with a support plate and a support collar. Install
it by screwing the support plate to the top of the prop-
erly framed ceiling joist opening, using screws provided.
A round trim plate (TP) is attached to the ceiling, using
screws, to provide a finished appearance once in-
stalled. (Fig. 35)

�����
�������
����������������
����

Ceiling Support
Plate

Ceiling Support
Collar

Trim Plate

ST923

Fig. 35 Ceiling support.

The Cathedral Ceiling Support (CCS) may be used in
pitched or flat ceiling installations and comes with a
support collar and a decorative two part square trim
plate. Install by inserting the support box down through
the framed joist opening (end with round hole first) in
the ceiling using tin snips, cut the corners of the open
end of the box such that the sides can be folded down
over the top of the joist framing members. Nail the
folded sides to the top of the framing. (Fig. 36)

�����
�������������������
����

Two Part Square
Trim Plate

Support Box

Support Box Collar

ST926

Fig. 36 Support box.

A two-part square trim plate is provided to give a fin-
ished look once installed. Simply fit the two halves of
the trim plate around the cathedral ceiling support box
hanging below the ceiling (overlapping if necessary)
and screw them to the ceiling. Both the ceiling support
and cathedral ceiling support can support a maximum
of 40’ (12 m) of pipe.

Offsets:
If any offsets are necessary in the vertical system, an
Offset Support (OS) should be installed directly above
the upper elbow of the offset. Install by attaching the
offset support band to the pipe with two #8 x 1/4” sheet
metal screws (minimum ) and secure the offset support
straps to surrounding structure. (Fig. 37)

�����
��������������������
����

Nail to top of
framing

Offset Support
Strap

Offset Support
Collar

ST927

Fig. 37 Offset support.

Supporting DIRECT-TEMP: Horizontal Support
Horizontal runs of Direct-Temp should be supported
every 4’ (122 cm) of pipe. This can be done with the use
of plumbers strapping or the offset support.
Adjustable Length (AJ)
An Adjustable Length is available to accommodate
installations where non-standard lengths are necessary.
The adjustable length telescopes down over a standard
length of pipe and provides an extension range of 3¹⁄₂”
(89 mm) to 10¹⁄₂” (267 mm). Install by sliding the inlet
end of the adjustable length over the outlet end of a
standard length of pipe. After positioning the adjustable
length appropriately, secure it to the standard length
with two (2) #8 x1/4” sheet metal screws (provided).
Seal the area between both the top and bottom of the
adjustable length outer wall and the outer wall of the
standard length with an approved silicone sealant.
Fire Stopping
DIRECT-TEMP must be firestopped wherever it passes
through floors, ceiling or walls. The only location where
a firestop is not required is at the roof level. Both verti-
cal support components with trim plates provide for
firestopping. The wall thimble also acts as a firestop.
at other locations, a firestop spacer (FS) should be in-
stalled. In the attic the firestop should be placed on top
of the joist framing to prevent debris from falling into the
joist framing. (Fig. 38)

Horizontal Installation

1. Determine the appliance location. Refer to the appli-
ance manufacturer’s installation instructions for clear-
ance to combustible requirements, termination options,
number of elbows, maximum length, etc. Then posi-
tion the appliance and plan vent routing accordingly.