Stardance direct vent/natural vent gas heater – Vermont Casting SDDVT User Manual

Page 23

Advertising
background image

23

Stardance Direct Vent/Natural Vent Gas Heater

20012734

Consider locating the appliance in a place where there
will be no interference with wall studs, electrical wir-
ing, conduit, plumbing pipe or other obstructions. The
termination should be located at least 12” (305 mm)
(Fig. 39) above grade, remain above the snow line in
geographical areas that accumulate snow and be away
from traffic areas such as walkways if it is less than 7’
(2.1 m) high. Refer to Pages 11, 12, Figures 11, 12 for
more detail.

�����
����������������
����

Firestop (FS)
Placed on Top
of Framed
Opening

Attic Framing
(No floor)

Maintain at Least
Minimum Clearance to
Combustibles, Wire and
Insulation

ST928

Fig. 38 Firestop spacer.

NOTE: As a general rule, the wall thimble is optional in
the U.S. However, there may be some manufacturers
that require it. Contact the appliance manufacturer for
information if uncertain. When installed in Canada, a
wall thimble is required on all installations in which
the vent passes through a combustible wall.
5. If required, install the outside half of the wall thimble
(WT) through the opening and screw or nail in place. (Fig.
40) Seal around the perimeter of the thimble face plate on
the exterior wall using an RTV silicone sealant to provide
protection from possible rain infiltration. (Fig. 40)

�����
�������������
����

Snorkel Termination

Window Well

12” (305 mm) Minimum
Clearance Above Grade Level to

Air Intake

Grade Level
Sloped Away
From Building

Adequate
Drainage as per
Local Codes

Maintain 2”
(51 mm)
Clearance
Below Snorkel

ST929

Fig. 39 Below grade installation.

�����
��������������������
����

Wall
Thimble
Shield

Seal with RTV
Silicone Sealant
on Exterior side
here (around
perimeter)

Wall Thimble
Shield

Wall
Thimble
Face
Plate

Wall Thimble
Face Plate

ST930

Fig. 40 Wall thimble.

2. Assemble the pipe (and elbow if using) and attach it
to the appliance. Plan for a level to 1/4” per foot rise (6
mm per 305 mm) (from inlet to outlet) in the horizontal
system if not specified by the appliance manufacturer.
Horizontal runs should be supported every 4’ (122 cm).
3. Push the appliance near the desired location. Deter-
mine the centerpoint of the penetration by locating the
centerline of the outlet of the pipe with respect to the wall.
4. Frame an opening to the dimension specified in the
Framing Dimension Table 1. Ensure the centerline of
the pipe lines up with the center of the prepared open-
ing unless otherwise specified by the appliance manu-
facturer.

NOTE: The wall thimble accommodates wall thickness-
es of 4¹⁄₂” (114 mm) to 7¹⁄₂” (191 mm). If a larger range
is needed due to a thicker wall, it is permissible to field
fabricate a metal sleeve extension and attach it to the
shields.
6. Install the horizontal termination to the exterior wall
using four (4) all purpose screws through the holes
located at each corner of the termination. Make sure
the arrow (embossed on the front of the termination)
is pointing up. (Fig. 41) If the house has vinyl siding,
a Vinyl Siding Standoff (VS) must be installed prior to
installing the horizontal termination. Refer to the appli-
ance manufacturer to determine if one is recommend-
ed. Attach the vinyl siding standoff to the exterior side
of the wall (making sure it is level and centered with
respect to the opening) with screws (provided) at each
corner of the standoff. Attach the horizontal termination
to the standoff. (Fig. 42)
If the wall is brick or concrete, and contains no com-
bustible material, a 7” (178 mm) round penetration
hole is adequate. The wall thimble is not required. The
perforated straps of the horizontal termination provide
a method of attachment. These can either be threaded
through the opening or wall thimble (if used) and
screwed to the pipe or removed with a pair of tin snips
if not used. Use proper masonry fasteners to attach the
horizontal termination to the wall.

Advertising