EVCO S.p.A. | Code 104R200E114 | Page 3 of 10 | PT 14/13 | version 1.1

5

ENERGY SAVING

5.1

Preliminary notes

Once the time you have set with parameter i10 has passed,
without activations of the door microswitch input (after the
cell temperature has reached the work set-point) the “en-
ergy saving” function is activated (until the input is activated
again).
During function “Energy Saving” the working set-point is
increased of the temperature you have set with parameter
r4 and the evaporator fan is turned on cyclically, on condition
that parameter F0 has value 1 or 2 (parameter F13 sets the
time the fan remains turned off and parameter F14 the time
it remains turned on).
It is also possible to activate the “energy saving” function in
remote mode through the digital inputs (with effect only on
the compressor).

6

“HACCP” FUNCTION

6.1

Preliminary notes

The device can memorise the following HACCP alarms:
-

minimum temperature alarm (code “AL”)

-

maximum temperature alarm (code “AH”)

-

door microswitch input alarm (code “id”)

The device supplies the following information for every alarm:
-

the critical value

-

the duration of the alarm (from 1 min to 99 hours and
59 min, partial if the alarm is in progress).

Code Critical value

AL

the minimum temperature of the cell during any
alarm of this type

AH

the maximum temperature of the cell during any
alarm of this type

id

the maximum cell temperature during any alarm
of this type; see also parameter i4

The device stored the minimum temperature alarm on con-
dition that the temperature associated to the alarm is that of
the cell (parameter A0 = 0).
if the device is switched off, no alarms will be stored.
The device updates the information regarding the alarms
provided the critical value of the new alarm is more critical
than that stored or provided the information has already
been displayed.
The “HACCP” LED provides information regarding the storage
status of the alarms; see paragraph 9.1.
6.2

Display of HACCP alarm information

To begin the procedure:
1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the

key down for 1 s: the display will show the

first label available.

3.

Press and release the

key or the

key to select

LS”.

4.

Press and release the

key: the display will show

one of the codes included in the table in paragraph 6.1.

If the device does not have any alarms stored, the label
LS” will not be displayed.
To select an alarm:
5.

Press and release the

or

key (to select, for

example, “AH”).

To see information regarding the alarm:
6.

Press and release the

key: the HACCP LED will

stop flashing and remain on permanently and the dis-
play will show, for example, the following information
in succession (for example):

Inform. Part

8.0

the critical value is 8.0 °C/8 °F

dur

the display is about to show the alarm duration

h01

the alarm lasted for 1 hour (other data continues)

n15

the alarm lasted 1 hour and 15 min

AH

the alarm selected

the displays each piece of information for 1 s.
To exit the information sequence:
7.

Press and release the

key: the display will show

the alarm selected (in the example “AH”).

To exit the procedure:
8.

Exit the information sequence.

9.1 Press and release the

or down

key until the

display shows the cell temperature or do not operate
for 60 sec.

Alternatively:
9.2 Press and release the

key.

7.3

Cancelling the HACCP alarm list

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the

key down for 1 s: the display will show the

first label available.

3.

Press and release the

key or the

key to select

rLS”.

4.

Press and release the

key.

5.

Press and release the

key or the

key within

15 s to set “149”.

6.

Press and release the

key or do not operate for

15 sec: the display will show a flashing “- - - -” for
4 sec and the “HACCP” LED switches off, after which
the device will exit the procedure.

If the device does not have any alarms stored, the label
rLS” will not be displayed.

7

COMPRESSOR OPERATING HOURS COUNT

7.1

Preliminary notes

The device can memorise up to 9.990 compressor operating
hours.
The parameter C10 establishes the number of operating
hours is higher than the limit at which the need for
maintenance is signalled.
7.2

Display of Compressor Operation Hours

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the key down for 1 s: the display will show the first
label available.

3.

Press and release the

key or the

key to select

CH”.

4.

Press and release the

key.

To exit the procedure:
5.

Press and release the

key or do not operate for

60 sec.

6.1 Press and release the

or down

key until the

display shows the cell temperature or do not operate
for 60 sec.

Alternatively:
6.2 Press and release the

key.

7.3

Cancelling the HACCP alarm list

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the

key down for 1 s: the display will show the

first label available.

3.

Press and release the

key or the

key to select

rCH”.

4.

Press and release the

key.

5.

Press and release the

key or the

key within

15 s to set “149”.

6.

Press and release the

key or do not operate for

15 sec: the display will show “- - -” flashing for
4 sec, after which the device will exit the procedure.

8

SETTINGS

8.1

Setting the working set-point

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Press and release the

key: the LED will flash.

3.

Press and release the

or

key within

15 sec; see also parameters r1, r2 and r3

4.

Press and release the

key or do not operate for

15 sec: the LED will switch off and then the device
will exit the procedure.

To exit the procedure before the operation is complete:
5.

Do not operate for 15 sec (any changes will be saved).

The working set-point can also be set via parameter SP.
8.2

Setting the configuration parameters

To begin the procedure:
1.

Make sure no procedures are in progress

2.

Hold the

key and the

key down for 4 s:

the display will show “PA”.

3.

Press and release the

key.

4.

Press and release the

key or the

key within

15 s to set “-19”.

5.

Press and release the

key or do not operate for

15 sec.

6.

Hold the

key and the

key down for 4 s:

the display will show “SP”.

To select a parameter:
7.

Press and release the

key or the

key.

To change a parameter:
8.

Press and release the

key.

9.

Press and release the

key or the

key within

15 sec.

10. Press and release the

key or do not operate for

15 sec.

To exit the procedure:
11. Hold down the

and

keys for 4 sec and do not

operate for 60 sec (any changes will be saved).

After changing the parameters, suspend power supply flow
to the device.
8.3

Restoring the Manufacturer’s Settings

To begin the procedure:
1.

Make sure no procedures are in progress

2.

Hold the

key and the

key down for 4 s:

the display will show “PA”.

3.

Press and release the

key.

4.

Press and release the

key or the

key within

15 s to set “149”.

5.

Press and release the

key or do not operate for

15 sec.

6.

Hold the

key and the

key down for 4 s:

the display will show “dEF”.

7.

Press and release the

key.

8.

Press and release the

key or the

key within

15 s to set “1”.

9.

Press and release the

key or do not operate for

15 sec: the display will show “dEF” flashing for
4 sec, after which the device will exit the procedure.

10. Cut the device power supply off.
To exit the procedure before the operation is complete:
11. Hold the

and

key down for 4 s during the

procedure (i.e. before setting “1”:
Restore will not be performed).

Make sure that the manufacturer’s settings are appropriate
(see chapter 13).

9

WARNING LIGHTS AND DIRECTIONS

9.1

Signals

LED

Part
compressor LED light
if the LED is on, then the compressor is on
if the LED is flashing:
-

the working set-point is in the process of
being changed (via the procedure described
in paragraph 8.1)

-

a compressor protection will be in progress;
see parameters C0, C1, C2, C14, C15, C16
and i7

Defrost LED
If it is on:
-

defrosting is in progress

-

predripping will be in progress; see
parameter d16

If the LED is flashing:
-

defrosting will be requested but a compres
sor protection will be in progress; see the
parameters C0, C1 and C2

-

dripping will be in progress; see parameter d7

-

the refrigerant fluid heating will be in
progress; see parameter d15

Evaporator fan LED light
if it is on:
-

the evaporator fan will be on

If the LED is flashing:
-

evaporator fan standstill will be in progress;
see parameter F3

AUX Auxiliary LED

If it is on:
-

the cell light will have been switched on in
manual mode (only if parameter u0/u1 is set
at 0)

-

the demister resistors will be switched on (only
if the parameter u0/u1 is set at 1)

-

the auxiliary output will have been switched
on in manual mode (only if parameter u0/u1

is

set at 2)

-

the door resistors will be switched on (only
if the parameter u0/u1 is set at 4)

-

the evaporator valve will be activated (only if
parameter u0/u1 is set at 5)

-

the condenser fan will be on (only if param-
eter u0/u1 is set at 6)

if the LED is flashing:
-

the cell light will have been switched on in
remote mode; see parameters i0 and i5 (only
if parameter u0/u1 is set at 0)

-

the auxiliary output will have been switched
on in remote mode; see parameters i0 and i5
(only if parameter u0/u1 is set at 1)

HACCP HACCP LED

if it is on, all information regarding HACCP alarms
has not been displayed
if it is flashing, the device has stored at least one
new HACCP alarm
if it is off, all information regarding the HACCP
alarms has been displayed or the list of alarms has
been cancelled
maintenance LED
if on, compressor maintenance will be requested;
see parameter C10
“overcooling” LED
if it is on, the “overcooling” function will be in
function; see parameters r5 and r6

°C

degree Celsius LED
if on, the temperatures will be displayed using the
degree Celsius grade unit of measurement; see
parameter P2
if flashing, the “energy saving” function is in progress
(with effect only on the compressor)