EVCO EVR274N9 User Manual

Page 4

Advertising
background image

EVCO S.p.A. | Code 104R200E114 | Page 4 of 10 | PT 14/13 | version 1.1

°F

degree Fahrenheit LED
if on, the temperatures will be displayed using the
degree Fahrenheit grade unit of measurement;
see parameter P2
if flashing, the “energy saving” function is in progress
(with effect only on the compressor)
On/stand-by LED
if it is on, the device will be off ( “stand-by”
state)
if it is off, the device will be on (“on” state)

9.2

Signal Descriptions/Explanations

Code Part

rhL

operation for a low percentage of relative humidity
in progress

rhH

operation for a high percentage of relative humidity
in progress

Loc

the keyboard is blocked; see paragraph 3.12
the work set-point is blocked; see parameter r3

- - -

the operation requested is not available

10

ALARMS

10.1

Alarms

Code Part

AL

Minimum alarm temperatures (HACCP alarms)
Solutions:
-

check the temperature associated to the
alarm; see parameters A0, A1 and A2

Main consequences:
-

if parameter A0 is set to 0, the device will
store the alarm

-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

AH

Maximum temperature alarm (HACCP alarms)
Solutions:
-

check the cell temperature; see parameters
A4 and A5

Main consequences:
-

the device will memorise the alarm

-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

id

Door microswitch input alarm (HACCP alarms)
Solutions:
-

check the causes of the activation of the in-
put; see parameters i0, i1, i5 and i6

Main consequences:
-

the effect established with the parameters i0
and i5

-

if parameter is set to 1, the device will store the
alarm, provided parameter i2 is not set to -1

-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

iA

Multifunction input alarm
Solutions:
-

check the causes of the activation of the in-
put; see parameters i0, i1, i5 and i6

Main consequences:
-

the effect established with the parameters i0
and i5

-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

iSd

Pressure switch alarm
Solutions:
-

check the causes of the activation of the in-
put; see parameters i0, i1, i5, i6, i7, i8 and i9

-

switch off and re-start the device or suspend
the power supply

Main consequences:
-

the regulators will switch off

-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

UA

Mains voltage alarm
Solutions:
-

check the mains voltage; see parameters C14,
C15 and C16

Main consequences:
-

the compressor will be switched off and will
not be switched on

CF

Compressor forced switch-on alarm
Solutions:
-

check the mains voltage; see parameter C18

Main consequences:
-

the device will perform forced compressor
switch-on; the device restores normal display
when the temperature of the cell reaches the
work set-point.

COH Condenser overheated alarm.

Solutions:
-

check the condenser temperature; see pa-
rameter C6

Main consequences:
-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

-

the condenser fan will be on (only if param-
eter u0/u1 is set at 6)

CSd

Condenser overheated alarm.
Solutions:
-

check the condenser temperature; see pa-
rameter C7

-

switch the device off and back on again: if
when the device is switched back on, the
temperature of the condenser is still higher
than that established in parameter C7, dis-
connect the power supply and clean the con-
denser

Main consequences:
-

the compressor and the evaporator fan will be
switched off

-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

-

the condenser fan will be on (only if param-
eter u0/u1 is set at 6)

dFd

Defrosting alarm switched off because maximum
time has been reached
Solutions:
-

heck the integrity of the evaporator probe;
see parameters d2, d3 and d11

-

press a key to restore normal display

Main consequences:
-

the device will continue to operate normally.

When the cause of the alarm disappears, the device restores
normal operation, except for the following alarms:
-

pressure switch alarm (code “iSd”) which requires the
switching off of the device or the temporary suspension
of the power supply

-

compressor blocked by condenser temperature alarm
(code “CSd”) which requires the switching off of the
device or the temporary suspension of the power supply

-

the compressor forced switch-on alarm (code “CF”)
that requires the cell temperature to have reached the
work set-point

-

Defrosting alarm switched off because maximum time
has been reached (code “dFd”) which requires the
pressing of a key.

11

ERRORS

11.1

Errors

Code Part

Pr1

Cell probe error
Solutions:
-

check that the probe is the PTC or NTC type;
see parameter P0

-

-

check the device-probe connection

-

check the cell temperature

Main consequences:
-

compressor activity will depend on param-
eters C4 and C5

-

the defroster will not be activated

-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

-

the door resistors will be switched off (only if
the parameter u0/u1 is set at 4)

-

the evaporator valve will be deactivated (only
if parameter u0/u1 is set at 5)

Pr2

Evaporator probe error
Solutions:
-

the same as the preceding case but with re-
spect to the evaporator probe

Main consequences:
-

if parameter P3 is set to 1, the defrosting
period will last for the amount of time set with
parameter 3

-

if parameter P3 is set to 1 and parameter d8
is set to 2 or to 3, the device will operate as if
parameter d8 were set to 0

-

if parameter F0 is set to 3 or 4, the device will
operate as if the parameter were set to 2

-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

Pr3

Condenser probe error.
Solutions:
-

the same as the preceding case but with re-
spect to the condenser probe

Main consequences:
-

condenser overheated alarm (code “COH”)
will not be activated

-

the compressor blocked alarm (“CSd” code)
will never be activated

-

the alarm output will be activated (only if
parameter u0/u1 is set at 3)

-

the condenser fan will operate parallel tot the
compressor (only if parameter u0/u1 is set at
6)

When the problem that caused the alarm disappears, the
device is restored to normal operation.

12

TECHNICAL DATA

12.1

Technical data

Purpose of the command device: operating command
device.
Construction of the command device: built-in electronic
device.
Case: grey self-extinguishing.
Dimensions: 180.0 x 38.0 x 44.0 mm (7.086 x 1.496 x
1.732 in; L x H x D).
Method of mounting the command device: panel, with
elastic retaining wings.
Protection rating: IP55.
Connections: 6.3 mm faston (0.248 in, power supply and
outputs), removable screw terminal board (inputs), 6 pole
connector (serial port).
The maximum length of the analogue input and digital input
connection cables must be less than 10 m (32.808 ft).
Operating temperature: from 0 to 55 °C (from 32 to 131 °F).
Storage temperature:from -25 to 70 °C (from -13 to
158 °F).
Humidity for use: from 10% to 90% relative humidity
without condensate.
Command device pollution situation: 2.
Power supply (according to the model):
-

115... 230 VAC (+10% -15%), 50/60 Hz, 5.5 VA max

-

230 VAC (+10% -15%), 50/60 Hz, 3 VA max.

Rated impulse voltage: 4K V.
Overvoltage category:
-

II in models with power supply of 115... 230 VAC

-

III in models with power supply of 230 VAC.

Class and structure of software: A.
Analogue inputs:
-

1 input (cell probe) in EVR221, EVR231, EVR261 and
EVR271 models, can be set via configuration parameter
for PTC/NTC probes

-

2 inputs (cell probe and evaporator probe) in EVR202,
EVR232, EVR203, EVR233, EVR263, EVR273, EVR204,
EVR234, EVR264 and EVR274 models, can be set via
configuration parameter for PTC/NTC probes.

PTC type analogue inputs (990 Ω @ 25°C, 77°F)
Type of sensor:

KTY 81-121.

Measurement field:

from -50 to 150 °C
(from -58 to 302°F).

Resolution:

0.1 °C (1 °F).

Protection:

none.

PTC type analogue inputs NTC (10K Ω @ 25°C, 77°F)
Type of sensor:

ß3435.

Measurement field:

from -50 to 105 °C (from -40
t

o

220 °C).

Resolution:

0.1 °C (1 °F).

Protection:

none.

Digital inputs: 1 input (door micro/multi-function 1 switch),
which can be set via configuration parameter due to normally
open contact/normally closed contact (free of voltage contact,
5 VDC, 2 mA)
Digital inputs
Power:

none.

Protection:

none.

Other inputs (in EVR204, EVR234, EVR264 and
EVR274 models only):
1 input that can be set via
configuration parameter for analogue input (condenser
probe)/digital input (door microswitch/multifunction 2), with
the same technical features illustrated previously.
Displays: custom 3 digit display with function icon.
Digital outputs:
1 output (electromechanical relay) in EVR221, EVR231,
EVR261 and EVR271 models
-

1 x 30 A res. output @ 250 VAC type SPST (K1) for
compressor management in models with power supply
of 115... 230 VAC, 1 x 16 A in-rush res. output @ 250
VAC type SPST (K1) for compressor management in
models with power supply of 230 VAC.

2 outputs (electromechanical relays) in EVR202 and EVR232
models
-

1 x 30 A res. output @ 250 VAC type SPST (K1) for
compressor management in models with power supply
of 115... 230 VAC, 1 x 16 A in-rush res. output @ 250
VAC type SPST (K1) for compressor management in
models with power supply of 230 VAC

-

1 x 8 A res. output @ 250 VAC type SPDT (K2) for
management of the cell light, demisting resistors, aux.
output, alarm output, door resistors, evaporator valve,
evaporator fan or defrost.