EVCO S.p.A.

EVSX815 | Installer manual ver. 1.3 | Code 144XS815E134

page 32 of 60

r7

-50.0

99.0

°C/°F (1)

0.0

work set-point during blast chilling; also work set-point

during the soft deep freezing phase (cabinet temperature);

see also parameter r0

r8

-50.0

99.0

°C/°F (1)

-40.0

work set-point during deep freezing (cabinet temperature);

see also parameter r0

r9

-50.0

99.0

°C/°F (1)

-20.0

work set-point during hard blast chilling phase (cabinet

temperature); see also parameter r0

r10

-50.0

99.0

°C/°F (1)

2.0

work set-point during post blast chilling storage (cabinet

temperature); see also parameter r0

r11

-50.0

99.0

°C/°F (1)

-20.0

work set-point during post deep freezing storage (cabinet

temperature); see also parameter r0

r12

-50.0

99.0

°C/°F (1)

5.0

work set-point during pre-cooling (cabinet temperature);

see also parameter r0

r13

-50.0

99.0

°C/°F (1)

15.0

end temperature of the temperature-controlled hard blast

chilling phase (temperature detected by the needle probe)

r14

10

100

%

60

duration of the time-controlled hard blast chilling phase

(intended as a percentage of the value established with

parameter r1); also duration of the time-controlled soft

deep freezing phase (intended as a percentage of the value

established with parameter r2)

r15

-50.0

99.0

°C/°F (1)

65.0

temperature below which the count of the maximum

temperature-controlled

blast

chilling

and

maximum

temperature-controlled

deep

freezing

is

started

(temperature detected by the needle probe)

r16

0

2

- - - -

1

type of operating cycle that can be selected

0 = blast chilling and storage

1 = blast chilling and storage or deep freezing and

storage

2 = deep freezing and storage