F16

-50.0

99.0

°C/°F (1)

20.0

evaporator temperature above which the evaporator fan is

off during pre-cooling, blast chilling and deep freezing (only

if parameter F0 is set at 1); see also parameter XS8 (10)

F17

-50.0

99.0

°C/°F (1)

90.0

cabinet temperature above which the evaporator fan is off

during pre-cooling, blast chilling and deep freezing (only if

parameter F0 is set at 1 or 2); see also parameter XS8

Par.

Min.

Max.

Unit

Default

Digital inputs

i0

0

2

- - - -

2

effect caused by opening the door, i.e. by activation of the

door micro switch (12)

0 = no effect

1 = the compressor and the evaporator fan will be off

and the cabinet light will be on. On expiry of the

time established with parameter i2, the display will

show the flashing “id” code and the buzzer will be

activated (until the door is closed); see also

parameter F15 (13)

2 = the evaporator fan will be off and the cabinet light

will be on. On expiry of the time established with

parameter i2, the display will show the flashing “id

code and the buzzer will be activated (until the door

is closed); see also parameter F15

i1

0

1

- - - -

0

type of door micro switch input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i2

-1

120

min

5

door open alarm signalling delay (“id” code); on expiry of

the time established with the parameter, the compressor

will be off

-1 = the alarm will not be signalled

i5

0

1

- - - -

1

effect caused by the activation of the high pressure input

0 = no effect

1 = the compressor and the evaporator fan will be off

and the condenser fan will be on. On expiry of the

time established with parameter i7, the display will

show the flashing “HP” code and the buzzer will be

activated (until the input is deactivated)