Troubleshooting flowcharts – FloAire F-D Installation User Manual

Page 28

Advertising
background image

28

Is Freeze-Stat

open?

Adjust or

Replace

Is end switch on

Motorized

Damper closed?

Adjust or

Replace
actuator

YES

YES

NO

Nothing

Happens

Is Overload

tripped on

starter?

Reset & measure FLA

of motor. Is it higher

than rating?

Adjust

or

change

Pulley

NO

NO

YES

Blower runs

but there is

no heat

Is the air flow LED

on Flame Saftey

illuminated?

Adjust pulley to

achieve proper

airflow.

NO

Is outside air cooler than

intake air thermostat

setting?

Proper

economizer

operation

YES

NO

Is High Temp.

Limit Tripped?

Reset

Is there a

Remote Panel

Installed?

Check wiring

Is Remote set to

"Heat"

Set Remote

Panel to

"Manual" and

"Heat" mode.

Refer to Flame

Safety Guide

YES

YES

YES

YES

NO

NO

NO

Burner lights but

heater stays in

Low Fire

Is there voltage on

Terminal #17

Replace

FSC

Are all valves

powered and open?

Check valve wiring

or open valves

With wires 3 & 4

removed from the

Maxitrol Amplifier, is

there 9.5K to 11K

Ohms between the

wires?

Replace

Discharge Air

Sensor

Remove Terminal #4

from the Maxitrol

Amplifier. Does the

heater go into High Fire?

Replace

Amplifier

With wires 1 & 2

removed from the

Maxitrol Amplifier, is

there 9.5K to 11K Ohms

between the wires?

Replace the

Temperature

Selector

Is there a short or open

circuit in Modulating

Valve? Should be 45-55
Ohms (60-80 on MR212)

Replace

Modulating

Valve

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

No

Burner lights but heater

stays in High Fire

Is there a jumper between

terminals 2 & 3 on the

Maxitrol Amplifier?

Install

Jumper

Is there a short circuit in

the Remote Temperature

Selector or wiring?

Repair short or

replace

Temperature

Selector

Is there an open circuit in

the Discharge Air Sensor

or wiring?

Repair Circuit or

replace the

Discharge Air

Sensor

Is Plunger in the

Modulating Valve jammed?

Inspect and clean. It

should operate freely in

the sleeve.

Foreign object holding

valve open. Remove

bottom plate and inspect

valve and seat. Clean or

replace valve.

No

No

No

No

Yes

Yes

Yes

Troubleshooting Flowcharts