Yearly – FloAire F-D Installation User Manual

Page 31

Advertising
background image

31

Burner Orifice

Drill Size

Orifice

Drill Size

Gas Port

31

Air Port

43

Optional Mixing Box Filters

Diagonal Filters

Unit Size

Filter Quantity

Filter Size

1

4 10 x 16

2

2 20 x 25

3

4 15 X 20

4

4 18 X 25

5

9 14.5 x 19

Vertical Filters

Unit Size

Filter Quantity

Filter Size

1

1 10 x 16

2

1 16 x 25

3

2 15 x 15

4

2 16 x 20

5

3 14.5 x 19

Yearly

1. Inspect bearings for wear and deterioration. Replace if necessary.
2. Inspect belt wear and replace torn or worn belts.
3. Inspect bolts and set screws for tightness. Tighten as necessary.
4. Inspect motor for cleanliness. Clean exterior surfaces only. Remove dust and

grease from the motor housing to ensure proper motor cooling. Remove dirt
and grease from the wheel and housing to prevent imbalance and damage.

5. Check for gas leaks and repair if present.
6. Clean flame sensor by rubbing with steel wool to remove any rust build-up,
7. Clean burner with a wire brush and insure burner ports are free of debris.

Then wipe the burner with a clean rag.