Check that all terminal screws are tight and that wires are in place
Check pulley alignment. Correct if necessary

Check that the power supply matches the nameplate

voltage, phase, and amperage

Record the voltage on the Start-Up Sheet

Check that the gas type and pressure matches the

nameplate type and pressure

Check that the gas type and pressure matches the

nameplate type and pressure

Contact the service department is the power or gas

supply needs to be changed in the field. Different parts
might be necessary for the change

Turn the remote panel switch to OFF if blower and burner

service switches were supplied

Set the temperature set point dial to the maximum
Turn the main power disconnect ON

Bump the blower motor starter to check the blower

wheel rotation

The decal is located on the blower housing
If the rotation is backwards turn off the power and

correct the wiring

The rotation can be corrected by interchanging two

legs of 3 phase (must be between vfd and motor on vav units)


ROTATION

DECAL