FloAire FAV User Manual

Page 19

Advertising
background image

19

Use the Amplifier to override the heater into high

fire.

On discharge temperature control amplifier

remove the #4 wire

On the space temperature control amplifier

remove the #2 and #4 wire

On the M-Series adjust the set-point to be

160 F

Adjust the manifold gas pressure to achieve the

desired discharge air temperature.

See the details for the high fire pressure

adjustment locations.

On manifolds with an MR212 modulation

valve, adjust the small regulator inside the
MR212 modulation valve

On manifolds with either an M511 or M611

modulation valve, adjust the regulator located
before the main gas valves

On manifolds with a combination gas valve,

adjust the regulator under the brass cap on
the combination gas valve.

Measure the discharge temperature using a

thermometer. Laser thermometers are not as
accurate as a thermocouple type.

If the discharge ductwork outlet is hard to reach,

you may feed a thermocouple into the mixing tube inside the blower discharge.


Setting High Fire – Manifold Pressure Method

Turn the burner service switch OFF
Measure the manifold pressure with the burner in high fire as described above
Adjust to match design manifold pressure on nameplate
Measure discharge temperature and calculate temperature rise as described above to account for

variances in airflow from design










HIGH FIRE

HIGH FIRE

HIGH FIRE

MR212

M511 & M611

36C68

GAS TYPE: NATURAL
MAX. TEMP. RISE: 140 F
DESIGN TEMP. RISE: 72 F
MAX. DISCHARGE TEMP.: 80
F