Use the DC terminals on the flame safety to read the pilot flame signal

Record the pilot flame signal in the Start-Up Sheet
Record the low and high fire flame signal on the Start-Up Sheet

Setting High Fire

Open the Burner Gas Shut Off Valve

Measure the intake air temperature.
Add the intake air temperature to the units nameplate design temperature rise.
This result will be the desired high fire discharge temperature.

Example: Intake Temp 70 F
Design Temp Rise

72 F

Discharge Temp

142 F

PILOT REGULATOR

OPEN VALVE

GAS TYPE: NATURAL
MAX. TEMP. RISE: 140 F
DESIGN TEMP. RISE: 72 F
MAX. DISCHARGE TEMP.: 80
F

POSITIVE TERMINAL

NEGATIVE TERMINAL

+

-