5. Slide the outdoor-air inlet screens into the screen track on

the hood side panels. While holding the screens in place,
fasten the screen retainer to the hood using the screws
provided. Repeat the process for the barometric exhaust
air screen. Do not attach completed (Fig. 30) hood as-
sembly to unit at this time.

6. Slide the EconoMi$er assembly into the rooftop unit. See

Fig. 31 and 32.

NOTE: Be sure to engage rear EconoMi$er flange under tabs in
return-air opening of the unit base. See Fig. 31.

7. Install the outdoor-air block-off plate, then secure the

EconoMi$er with the screws provided. See Fig. 32.

8. Remove and discard the 12-pin jumper plug from the unit

wiring harness located in the upper left corner and insert
the EconoMi$er plug into the unit wiring harness. Refer
to wiring diagrams Fig. 33 and 34. Also refer to Fig. 35 if
installing an accessory power exhaust.

9. Install the complete hood assembly on the unit and secure

using the screws provided.

10. Remove the indoor fan motor access panel. See Fig. 36.

11. Mount the supply-air temperature sensor to the lower

left portion of the indoor blower housing with the
two (2) screws provided (see Fig. 37). Connect the violet
and pink wires to the corresponding connections on the
supply-air temperature sensor. Replace the indoor fan
motor access panel.

SEAL STRIP

SEAL STRIP

OUTDOOR AIR
HOOD TOP

SCREEN
RETAINER

OUTDOOR AIR
INLET
SCREENS

OUTDOOR AIR
HOOD SIDES

ASSEMBLED
EXHAUST HOOD

OUTDOOR AIR
OPENING
PANEL

Fig. 29 — Outdoor-Air Hood Assembly

WIRING
HARNESS

OUTDOOR
AIR
BLOCK-OFF
PLATE

Fig. 32 — EconoMi$er Installed

ECONOMI$ER

ECONOMI$ER REAR
FLANGE

UNIT BASE

UNIT FILTER
RACK

ECONOMI$ER CLIP
HVAC UNIT

Fig. 31 — Rear EconoMi$er Flange Installation

Fig. 30 — Completed Hood Assembly