Fig. 6 — base unit dimensions – Carrier 48TJD User Manual

Page 8

Advertising
background image

8

UNIT
48TJ

STANDARD

UNIT

WEIGHT

DURABLADE

ECONOMIZER

WEIGHT

ECONOMI$ER

WEIGHT

CORNER

WEIGHT

(A)

CORNER

WEIGHT

(B)

CORNER

WEIGHT

(C)

CORNER

WEIGHT

(D)

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

E/F004

460

209

34

15.4

47

21.3

140

63.5

105

47.6

159

72.1

56

25.4

D/E/F005

470

213

34

15.4

47

21.3

142

64.4

106

48.1

162

73.5

60

27.2

D/E/F006

490

222

34

15.4

47

21.3

150

68.0

115

52.2

160

72.6

65

29.5

D/E/F007

565

256

34

15.4

47

21.3

165

74.8

136

61.7

200

90.7

64

29.0

CONNECTION SIZES

A

1

1

/

16

″″″″ Dia [27] Field Power Supply Hole

B

3

/

4

″″″″-14 NPT Condensate Drain

C

1

/

2

″″″″-14 NPT Gas Connection

NOTES:

1. Dimensions in [

] are in millimeters.

2.

Center of gravity.

3.

Direction of airflow.

4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal dis-

charge units, field-supplied flanges should be attached to horizontal discharge openings, and all
ductwork should be attached to the flanges.

5. Minimum clearance (local codes or jurisdiction may prevail):

a. Between unit, flue side and combustible surfaces, 36 inches.
b. Bottom of unit to combustible surfaces (when not using curb), 1 inch.

Bottom of base rail to combustible surfaces (when not using curb) 0 inches.

c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater

clearance is optional.

d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC.
f.

Between unit and ungrounded surfaces, control box side, 36 in. per NEC.

g. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in.

per NEC.

h. Horizontal supply and return end, 0 inches.

6. With the exception of the clearance for the condenser coil and combustion side as stated in notes

5a, b and c, a removable fence or barricade requires no clearance.

7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering

material if set on base rail.

8. The vertical center of gravity is 1

′-6″ [457] up from the bottom of the base rail.

BOTTOM POWER CHART, THESE HOLES REQUIRED FOR

USE WITH ACCESSORY PACKAGES — CRBTMPWR001A00,

(POWER AND CONTROL) AND CRBTMPWR003A00

(POWER, CONTROL, AND GAS)

THREADED

CONDUIT SIZE

WIRE

USE

REQURED

HOLE SIZES (MAX.)

1

/

2

″″″″

24 V

7

/

8

″″″″ [22.2]

3

/

4

″″″″

Power

1

1

/

8

″″″″ [28.4]

1

/

2

″″″″ FPT

Gas

1

1

/

4

″ ″

″ [31.8]

Fig. 6 — Base Unit Dimensions