Figure v, Gidm series – I.C.E. GIDM-325 User Manual

Page 22

Advertising
background image

LINKAGE OPERATION (GRAVITY VENT)

BURNER
DAMPER

BUTTERFLY
DAMPER

ARM

LOW FIRE
SET SCREW

HIGH FIRE
SET SCREW

BUTTERFLY DAMPER PIN

HIGH FIRE

TRAVEL

POP UP DOOR

PRESSURE

TEST PORT

GIDM - LINKAGE SET-UP

( DECREASE THE DISTANCE BETWEEN DRIVE ROD AND CENTER PIN).

3. TO INCREASE COMBUSTION AIR MOVE DRIVE ROD TOWARDS CENTER PIN

2. TO INCREASE EXHAUST MOVE DRIVE ROD TOWARD DAMPER PIN

1. INSTALL A MANOMETER ON POSITIVE AT TEST PORT IN POP-UP DOOR.

(DECREASE THE DISTANCE BETWEEN DRIVE ROD AND CENTER PIN.)

A) INSURE THERE IS A PRESSURE AT THAT POINT ON LOW

FIRE THROUGH TO HIGH FIRE. MAXIMUM 1.50" W.C.

YOU MAY HAVE TO SPEED UP EXHAUST AND OR BURNER DAMPER TO

4. TO INSURE A POSITIVE PRESSURE THROUGHOUT FULL MODULATION RANGE,

MATCH GAS FLOW TO THE BURNER.

MOVE DRIVE ROD CLOSER TO THE DRIVE PIN ON THE BUTTERFLY VALVE.

( THIS WILL REDUCE THE MOVEMENT OF THE BURNER DAMPER)

VALVE.

5. ADJUST LOW AND HIGH FIRE ON THE STOP SCREWS ON THE BUTTERFLY

NOTE:

THE MOTOR IS ALLOWED TO OVER RUN WITH THE SPRINGS LINKAGE SET THE
TRAVEL ON THE PENN JOHNSON MOTOR TO INSURE IT DOES NOT GO TO FAR

OR DAMAGE TO THE MOTOR COULD OCCUR.

ADJUSTMENTS ARE MADE WITH THE SYSTEM IN OPERATION.

THE PROPORTIONAL BAND ADJUSTMENT, LOCATED ON THE TERMINAL

TURN THE PROPORTIONAL BAND ADJUSTMENT UNTIL THE SYSTEM

STABILIZES AND THE MOTOR ACTUATOR NO LONGER OSCILLATES.

PROPORTIONAL BAND

SET POINT

THE R81'S TERMINAL BOARD AND HAS A CALIBRATED DIAL

THE SET POINT FOR THE REMOTE SENSOR IS LOCATED ON

ADJUSTMENT

THAT IS ADJUSTABLE BETWEEN 40 AND 90°F (5 AND 30°C).

BOARD, IS ADJUSTABLE BETWEEN 2 AND 30°F (1.1 TO 16.7FC). FIELD

WITH DISCHARGE AIR SENSOR AND SELECTION ON MOTOR
ELECTRONIC BOARD.

STANDARD PENN JOHNSON MODULATION SYSTEM

NOTE:

8

10

X

XR

XD

T1

I

N

C T R

A

V

E

L

SET POINT

P

B

I N

C

24 V.A.C.

R

B

A91, T91

THERMISTOR

SENSOR

M100 WITH R81Q

2

S

S

1

2

T

JUMPER

POWER SUPPLY

FIG. 4 - TYPICAL WIRING HOOKUP FOR THE
R81QAA INSTALLED IN AN M100 SERIES
MOTOR ACTUATOR.

JOB NO.

DRW. NO.

SCALE

REV

DATE

CHK. BY

ISSUED BY

DRAWN BY

TITLE

Rev By

Revision Description

Date

GIDM GRAVITY VENTED LINKAGE OPERATION

GIDM

SERIES

JV

JULY 1/98

1:1

FIG. V

-