Table 4 — ICVC Alert Codes (cont)

NORMAL RUN WITH OVERRIDES

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or

alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

ICVC FAULT

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

120

RUN CAPACITY
LIMITED

HIGH CONDENSER
PRESSURE

120

Condenser Pressure

[VALUE] exceeded limit of
[LIMIT]*.

Check condenser water pump operation.
Check for high condenser water temperatures or
low flow rate. Verify that isolation valves are
open.
Check Cond Press Override setting in SETUP1.

121

RUN CAPACITY
LIMITED

HIGH MOTOR
TEMPERATURE

121

Comp Motor Winding

Temp [VALUE] exceeded
limit of [LIMIT]*.

Check for closed valves or restriction in motor
cooling lines.
Check for closed refrigerant isolation valves.
Check Comp Motor Temp Override setting in
SETUP1.

122

RUN CAPACITY
LIMITED

LOW EVAP REFRIG
TEMP

122

Evaporator Refrig

Temp [VALUE] exceeded
limit of [LIMIT]*.

Check refrigerant charge.
Check that optional cooler liquid line isolation
valve is fully open.
Check for excessive condenser flow or low
chilled water flow.
Check for low entering cooler temperature.
Check that condenser inlet and outlet water
nozzles are piped correctly.
Check for waterbox division plate gasket bypass.

123

RUN CAPACITY
LIMITED

HIGH COMPRESSOR
LIFT

123

Surge Prevention

Override: Lift Too High For
Compressor

Check for high condenser water temperature or
low suction temperature.
Check for high Evaporator or Condenser
approaches.
Check surge prevention parameters in
OPTIONS screen.

124

RUN CAPACITY
LIMITED

MANUAL GUIDE VANE
TARGET

124

Run Capacity Limited:

Manual Guide Vane Target.

Target Guide Vane Position has been forced in
the COMPRESS screen. Select and RELEASE
force to return to normal (automatic) operation.

125

RUN CAPACITY
LIMITED

LOW DISCHARGE
SUPERHEAT

No Alert message.

Check for oil loss or excess refrigerant charge.
Verify that the valves in the oil reclaim lines are
open.

126

RUN CAPACITY
LIMITED

HIGH RECTIFIER TEMP 126

Rectifier Temperature

[VALUE] exceeded limit of
[LIMIT]*.

Check Rectifier Temp Override in SETUP1
screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid.
Check for proper VFD cooling fan operation and
blockage.

127

RUN CAPACITY
LIMITED

MANUAL SPEED
CONTROL

No Alert message.

Chiller is not in automatic temperature control.

128

RUN CAPACITY
LIMITED

HIGH INVERTER TEMP

128

Inverter Temperature

[VALUE] exceeded limit of
[LIMIT]*.

Check Inverter Temp Override in SETUP1
screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid.
Check for proper VFD cooling fan operation and
blockage.