Carrier 19XRV User Manual

Page 14

Advertising
background image

14

Table 4 — ICVC Alert Codes (cont)

CHILLER ALERTS (cont)

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or

alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

ICVC FAULT

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

159

SENSOR ALERT

SPARE TEMPERATURE
#2

159

Spare Temperature 2

[VALUE] exceeded limit of
[LIMIT]*.

Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check Spare Temp #2 Limit in SETUP1 screen.

161

LOSS OF
COMMUNICATION

WITH WSM

161

WSM Cool Source —

Loss of Communication.

Check settings in WSMDEFME screen.
Check CCN communications link with WSM
(Water System Manager) Module.
Check Supervisory Part of WSM.

162

SENSOR ALERT

EVAPORATOR
APPROACH

162

Evaporator Approach

[VALUE] Exceeded Limit of
[LIMIT]*.

Check that refrigerant charge level is adequate,
waterbox division plate gaskets are sealing,
evaporator tubes are not fouled and that oil
reclaim system is working.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check Evap Approach Alert setting in SETUP1
screen.

163

SENSOR ALERT

CONDENSER APPROACH 163

Condenser Approach

[VALUE] Exceeded Limit of
[LIMIT]*.

Check sensors resistance or voltage drop.
Check for proper wiring.
Check Cond Approach Alert setting in SETUP1
screen.
Check for noncondensable gas in the
condenser.
Check that the condenser tubes are not fouled.

164

VFD SPEED ALERT LOW VFD SPEED

164

Actual VFD Speed

exceeded limit of Target VFD
Speed –10%.

Actual VFD Speed on COMPRESS screen must
be at least 90% of Target VFD Speed.

165

AUTORESTART
PENDING

LOW DC BUS VOLTAGE

165

Low DC Bus Voltage:

[VALUE] Exceeded Limit of
[LIMIT]*.

Verify phase to phase and phase to ground line
voltage.

166

AUTORESTART
PENDING

HIGH DC BUS VOLTAGE

166

High DC Bus Voltage:

[VALUE] Exceeded Limit of
[LIMIT]*.

Verify phase to phase and phase to ground line
voltage. Monitor AC line for high transient volt-
age conditions.

167

SYSTEM ALERT

HIGH DISCHARGE TEMP

167

Comp Discharge Temp

[VALUE] exceeded limit of
[LIMIT]*.

Check sensor resistance or voltage drop.
Check for proper wiring.
Check for excessive starts.
Check Comp Discharge Alert setting in SETUP1
screen.

168

SENSOR ALERT

HUMIDITY SENSOR
INPUT

168

Sensor Fault: Check

Humidity Sensor Input Sensor.

Check humidity sensor wiring on CCM connec-
tors J3 and J5. CCM switch SW2-1 must be in
“OFF” position.
Check Humidity Sensor Input in Controls Test.