5

Refrigerant Charge

The 38HDF and 38QRF units can be matched with multiple

outdoor units and thus additional charge might be required when
matched with the 40QNC or 40QNQ units.

Table 6 – Additional Charge

Additional Charge lb (kg)

Unit Size

38HDF

38QRF

018

1.2 (0.55)

0.8 (0.36)

024

1.0 (0.45)

0.5 (0.23)

030

2.4 (1.1)

0

036

0

0

Note:The above additional charge is required amount for line lengths up to

25 ft (7.6 m). For line lengths exceeding 25 ft (7.6 m), additional charge will

be required. Refer to the

Duct Free Splits Long Line Guide.

Metering Device

The metering device(s) for these systems is a type B Accurator
installed with the outdoor unit. One Accurator is required for the

cooling only system and two are required for the heat pump
systems. The Accurators are supplied with the outdoor unit.

However, since the same outdoor unit can be matched with
multiple indoor units, the correct Accurator must be selected. Refer

to Table 7 for the correct Accurator size.

Table 7 – Accurator Sizes

System Type

Size

Cooling

Accurator

Heating

Accurator

Cooling Only

018

49

---

024

55

---

030

63

---

036

70

---

Heat Pumps

018

49

45

024

55

49

030

63

53

036

70

63

Power and Connecting Cables -- Field Supplied

Power:

S

The indoor and outdoor units require a dedicated power supply.

S

Consult local building codes, NEC (National Electric Code) or
CEC (Canadian Electric Code) for any special requirements.

S

Use Table 8 for the electrical requirements for the outdoor units
and Table 9 for the indoor units to correctly size the cables and
disconnect switches.

Table 8 – 38HDF / QRF Electrical Requirements

Unit

Size

Voltage

38HDF

38QRF

Min Ckt Amps/

Fuse HACR Bkr

Amps

Min Ckt Amps/

Fuse HACR Bkr

Amps

018

208/230---1---60

12.1/20

12.1/20

024

208/230---1---60

16.8/25

16.8/25

030

208/230---1---60

18.4/30

18.4/30

036

208/230---1---60

23.8/40

23.8/40

036

208/230---3---60

18.0/30

18.0/30

036

460---3---60

8.3/15

8.3/15

Table 9 – 40QNC / QNQ Electrical Requirements

Unit

Size

Voltage

40QNC

40QNQ

Min Ckt Amps/

Fuse HACR Bkr

Amps

Min Ckt Amps/

Fuse HACR Bkr

Amps

018

208/230---1---60

0.48/15

0.48/15

024

208/230---1---60

0.48/15

0.48/15

030

208/230---1---60

0.48/15

0.48/15

036

208/230---1---60

0.55/15

0.55/15

Control Wiring

Thermostat wires should be used for control wiring between the

indoor and outdoor units. A two conductor cable is required for
the cooling only units and a seven conductor cable is required on

heat pumps. 18 AWG is recommended for any length up to 50 ft
(15.2 m). 16 AWG is recommended for lengths between 50 and

200 ft (15.2 and 61.0 m).

User Interface

The indoor unit is supplied with a wireless remote control. The

following accessories are also available

S

Wall mounted control. Up to 6 units can be daisy chained and
controlled by one wired control.

S

Zone manager capable of controlling up to 32 units divided up
to 8 different zones.

Operating Range

Ensure that the system operates within the application guidelines
shown in Table 10.
Cooling Operating Range

Maximum

Minimum

DB ° F (° C)

WB ° F (° C)

DB ° F (° C)

WB ° F (° C)

Outdoor

Unit

125 (51.7)

--- ---

55 (12.8)

--- ---

Indoor

Unit

90 (32.2)

74 (23.3)

62 (17.0)

56 (13)

Heating Operating Range

Maximum

Minimum

DB ° F (° C)

WB ° F (° C)

DB ° F (° C)

WB ° F (° C)

Outdoor

Unit

75 (23.9)

67 (19.4)

17 (---8.3)

--- ---

Indoor

Unit

81 (27.2)

--- ---

62 (17.0)

--- ---

Accessories

An extensive list of field installed accessories is available for both

indoor and outdoor units. Identify what accessories, if any, are
required for the application at hand and consult the separate

installation instructions for the accessories.

Some of the

accessories, especially on the indoor units, can be installed much
easier if planned ahead.