Table 3 — electrical data – Carrier 50ZH024-060 User Manual

Page 10

Advertising
background image

Table 3 — Electrical Data

UNIT

50ZH

NOMINAL

V-PH-Hz

IFM

TYPE

VOLTAGE

RANGE

COMPRESSOR

OFM

FLA

IFM

FLA

HEATER

PACKAGE NO.

ELECTRIC

HEAT

POWER

SUPPLY

DISCONNECT

SIZE

Min

Max

RLA

LRA

Nominal

kW*

FLA

MCA

MOCP

FLA

LRA

024

208/230-1-60

Std

187

254

12.8

63.0

0.9

2.4

None

—

—

19.3/ 19.3

25/ 25†

19/ 19

70/ 70

CPHEATER026A00

3.8/ 5.0 18.3/20.8

42.2/ 45.3

45/ 50†

40/ 42

89/ 91

CPHEATER024A00

7.5/10.0 36.1/41.7

64.4/ 71.4

70/ 80

60/ 66

107/112

030

208/230-1-60

Std

187

254

14.4

73.0

1.5

2.4

None

—

—

21.9/ 21.9

30/ 30†

21/ 21

83/ 83

CPHEATER026A00

3.8/ 5.0 18.3/20.8

44.8/ 47.9

45/ 50†

42/ 45 101/103

CPHEATER024A00

7.5/10.0 36.1/41.7

67.0/ 74.0

70/ 80

63/ 69

119/124

CPHEATER040A00

11.3/15.0

54.3/62.5

89.8/100.0

90/110

83/ 93 137/145

036

208/230-1-60

Std

187

254

17.7

93.0

1.5

2.8

None

—

—

26.4/ 26.4

35/ 35†

25/ 25 103/103

CPHEATER026A00

3.8/ 5.0 18.3/20.8

49.3/ 52.4

50/ 60†

46/ 49 121/123

CPHEATER024A00

7.5/10.0 36.1/41.7

71.6/ 78.6

80/ 80

67/ 73 139/144

CPHEATER040A00

11.3/15.0

54.3/62.5

94.3/104.6

100/110

88/ 97 157/165

208/230-3-60

Std

187

254

10.3

77.0

1.5

2.8

None

—

—

17.2/ 17.2

20/ 20†

17/ 17

87/ 87

CPHEATER029A00

3.8/ 5.0 10.5/12.0

30.3/ 32.2

35/ 35†

29/ 31

97/ 99

CPHEATER030A00

7.5/10.0 20.8/24.1

43.2/ 47.3

45/ 50†

41/ 45

107/111

CPHEATER032A00

11.3/15.0

31.4/36.1

56.4/ 62.3

60/ 70

53/ 58

118/123

042

208/230-1-60

Std

187

254

21.5

103.0

1.5

2.8

None

—

—

31.2/ 31.2

40/ 40†

30/ 30

113/113

CPHEATER026A00

3.8/ 5.0 18.3/20.8

54.1/ 57.2

60/ 60†

51/ 54 131/133

CPHEATER024A00

7.5/10.0 36.1/41.7

76.3/ 83.3

80/ 90

71/ 78 149/154

CPHEATER040A00

11.3/15.0

54.3/62.5

99.1/109.3

100/110

92/102 167/175

CPHEATER028A00 15.0/20.0 72.1/83.3 121.3/135.3 125/150

113/125

185/196

208/230-3-60

Std

187

254

12.4

88.0

1.5

2.8

None

—

—

19.8/ 19.8

25/ 25†

19/ 19

98/ 98

CPHEATER029A00

3.8/ 5.0 10.5/12.0

32.9/ 34.8

35/ 35†

31/ 33

108/110

CPHEATER030A00

7.5/10.0 20.8/24.1

45.8/ 49.9

50/ 50†

43/ 47

118/122

CPHEATER032A00

11.3/15.0

31.4/36.1

59.1/ 64.9

60/ 70

55/ 61 129/134

CPHEATER041A00 15.0/20.0 41.6/48.1

71.8/ 79.9

80/ 80

67/ 75 139/146

048

208/230-1-60

Std

187

254

28.2

129.0

1.5

4.2

None

—

—

41.0/ 41.0

50/ 50†

39/ 39 143/143

CPHEATER038A00

3.8/ 5.0 18.3/20.8

63.8/ 67.0

70/ 70

60/ 63 161/163

CPHEATER024A00

7.5/10.0 36.1/41.7

86.1/ 93.1

90/100

81/ 87 179/184

CPHEATER040A00

11.3/15.0

54.3/62.5

108.8/119.1

110/125

101/111

197/205

CPHEATER028A00 15.0/20.0 72.1/83.3 131.1/145.1 150/150

122/135 215/226

208/230-3-60

Std

187

254

13.5

99.0

1.5

4.2

None

—

—

22.6/ 22.6

30/ 30†

22/ 22

113/113

CPHEATER029A00

3.8/ 5.0 10.5/12.0

35.7/ 37.6

40/ 40†

34/ 36 123/125

CPHEATER030A00

7.5/10.0 20.8/24.1

48.6/ 52.7

50/ 60†

46/ 50 133/137

CPHEATER032A00

11.3/15.0

31.4/36.1

61.8/ 67.7

70/ 70

58/ 64 144/149

CPHEATER041A00 15.0/20.0 41.6/48.1

74.6/ 82.7

80/ 90

70/ 77 154/161

060

208/230-1-60

Std

187

254

27.7

170.0

3.1

6.2

None

—

—

43.9/ 43.9

60/ 60†

43/ 43 192/192

CPHEATER038A00

3.8/ 5.0 18.3/20.8

66.8/ 69.9

70/ 70

64/ 66 210/213

CPHEATER024A00

7.5/10.0 36.1/41.7

89.1/ 96.1

90/100

84/ 91 228/233

CPHEATER040A00

11.3/15.0

54.3/62.5

111.8/122.1

125/125

105/114

246/254

CPHEATER028A00 15.0/20.0 72.1/83.3 134.1/148.1 150/150

125/138 264/275

208/230-3-60

Std

187

254

15.9

124.0

3.1

6.2

None

—

—

29.2/ 29.2

35/35†

29/ 29 146/146

CPHEATER029A00

3.8/ 5.0 10.5/12.0

42.3/ 44.2

45/45†

41/ 43 156/158

CPHEATER030A00

7.5/10.0 20.8/24.1

55.2/ 59.3

60/60†

53/ 57 167/170

CPHEATER032A00

11.3/15.0

31.4/36.1

68.4/ 74.3

70/80

65/ 70 177/182

CPHEATER041A00 14.9/19.9 41.4/47.9

80.9/ 89.1

90/90

77/ 84 187/194

460-3-60

Std

414

508

8.0

60.0

1.5

3.2

None

—

—

14.7

20†

15

68

CPHEATER034A00

5.0

6.0

22.2

25†

22

74

CPHEATER035A00

10.0

12.0

29.7

30†

28

80

CPHEATER036A00

15.0

18.0

37.2

40†

35

86

CPHEATER037A00

20.0

24.1

44.8

45†

42

93

LEGEND

FLA

— Full Load Amps

HACR

— Heating, Air Conditioning and Refrigeration

IFM

— Indoor-Fan Motor

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

— National Electrical Code

OFM

— Outdoor-Fan Motor

RLA

— Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v or 480 v. If

power distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.

†Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load

and equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.

Use the following formula to determine the percentage of voltage

imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 240-3-60

AB = 235 v
BC = 242 v
AC = 236 v

235 + 242 + 236

Average voltage =

3

= 238

Determine maximum deviation from average voltage:

(AB) 238 − 235 = 3 v
(BC) 242 − 238 = 4 v
(AC) 238 − 236 = 2 v

Maximum deviation is 4 v.
Determine percentage of voltage imbalance:

4

% Voltage imbalance = 100 x

238

= 1.68%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%
contact your local electric utility company immediately.

10

Advertising