2.0

Cable Requirements

RS-232 Serial Cable
•

three conductor, shielded, stranded, AWG 24 wire (Belden 9533 or a larger gauge)

•

50 foot maximum length (per RS-232 industry specification - greater lengths are not recommended)

RS-485 Network Cable
•

one twisted, shielded pair of conductors, stranded, AWG 24 wire (Belden 9501 or a larger gauge)

•

4,000 foot total network length (per RS-485 industry specification)

•

extended network configurations are possible – refer to the Network Wiring Application Note (P/N 01824-002) for
extended network configurations of up to 5,000 feet per star line and 16,000 feet total network length

Telephone
•

1 pair copper phone line

NOTE: EntraGuard Titanium is not to be used with a Centrex, PBX, or digital phone line. Only use a Plain Old
Telephone Service (POTS) analog phone line.

Input Power
•

two conductor, stranded, AWG 18 wire (Belden 8461 or a larger gauge)

NOTE: On long power cable runs, the cable resistance causes a drop in voltage at the end of the cable run. Be sure your
power supply does provide 12 VDC at the end of the cable run.

Earth Ground

•

Single conductor, AWG 18 wire (or a larger gauge)

1

Input and Output Connections
•

two conductor, stranded, AWG 22 (or a larger gauge)

NOTE: The Lock Output relay may require a heavier gauge of wire depending upon the current demands of the lock and
the length of the lock wiring run.

NOTE: If plenum cable is required, please reference the Belden plenum equivalent to the cables listed above.

1. Ground wire is green, with or without yellow tracer.