LAARS EBP 175 MBTU/h - Installation, Operation and Maintenance Instructions User Manual

Page 25

Advertising
background image

Endurance

Page 25

6.6 Other Control Functions

6.6.1 Using Buttons on Control

Figure 30 shows a drawing of the control,

including the placement of the four buttons.

Table 4

shows the actions associated with each of the buttons.

6.6.2 Alarm Acknowledge

When an alarm is activated (LO or one of the F

codes), the control will flash between the alarm display

and the supply temperature. Pressing the power button

(upper left button) for half a second will allow the user

to scroll through the menus for 30 seconds, before

reverting back to the alarm display.

6.6.3 Power On/Off

Pressing the power button on the control (upper

left button) for 3 seconds will turn the controller off.

This will not de-energize the boiler’s power, but will

de-energize the controller. The display will still work,

but the boiler will not acknowledge a call for heat, and

will not be able to fire. This allows the user to check

and set parameters when the boiler is unable to fire.

The display will show “OFF”. When the power button

is pressed again for 3 seconds, the display will show

“ON” briefly, and the boiler will then resume normal

operation.

6.6.4 Low Fire Hold

By pressing and holding the enter button and

the down arrow button for 2 seconds, the user will fix

the Endurance in low fire for 5 minutes. There is no

change in the boiler control display when the unit is in

this mode.

6.6.5 High Fire Hold

By pressing and holding the enter button and the

up arrow button for 2 seconds, the user will fix the

Endurance in high fire for 5 minutes. This can be used

to check and/or set combustion on the appliance. There

is no change in the boiler control display when the unit

is in this mode.

6.6.6 Pump Operation

The Endurance’s internal pump will operate

when any of the following conditions occur:

Low temperature mode.

Tank charge mode.

Heating system (T-T) call for heat.

Domestic hot water (DHW) call for heat.

Error condition detected.

Supply temperature detected as less than

“boiler on point”.

6.6.7 Anti-Condense Valve Operation

The control on the Endurance opens and closes

during a call for heat, and the call for heat continues,

this differential will determine at what point below

the Burner Control Point the Endurance will energize

again. The differential is fixed at 13°F (7°C) to ensure

that the transfer tank will be properly charged.

6.5 Calculated Control Values

There are several control values that are not

directly set by the user, but are calculated by the boiler

control, once the user has set the parameters in

Section

6.4.

These do not show on the control display, but it

is helpful to know how they affect the control logic of

the Endurance units.

6.5.1 ACV Release

When the Endurance is in tank charge mode, and

there is a call for space heating, the boiler needs to

know at what temperature it can release the ACV (anti-

condensing valve) back to the space heating position,

allowing the hot water to go into the system. The ACV

release point is the “burner off” point minus 5°F (3°C).

For example, if the “burner off” point is 190°F (88°C),

the ACV release point is 185°F (85°C). This means

that when the supply temperature reads 185°F (85°C)

in the tank, it will release the ACV for heating mode.

6.5.2 Tank Charge Setting

When the temperature at the tank sensor goes

below the tank charge setting, the Endurance will be

in “tank charge” mode. The tank charge setting equals

the programmed “burner off” point minus a fixed

40°F (22°C) differential. For example, if the “burner

off” point is 190°F (88°C), the Endurance will go into

“tank charge” mode when the tank sensor reads below

150°F (66°C). The ACV will close, and will run to

bring the supply temperature up to 185°F (85°C), and

the ACV will be released back to the space heating

mode (as long as there is no call for domestic hot

water).

6.5.3 Burner On Point

The “Burner On” point is calculated by

subtracting the “Burner On Differential (Dif)” from

the “Burner Control Point.” The differential is fixed at

13°F (7°C). This value tells the Endurance when to re-

energize during a call for heat in which the Endurance

reached its “Burner Off Point.”

6.5.4 Modulation Point

During a call for heat, the Endurance will ignite

at low fire and will begin to modulate to match the

load as it approaches the “Burner Control Point.”

There is no fixed temperature when this will occur, and

this value is not displayed on the Endurance.

Advertising
This manual is related to the following products: