7.2 Filling the System

1. Open all supply and return valves.

2. Fill heating system to minimum operating

pressure 12 psig.

3. Loosen screw in coin vent and allow any trapped

air to escape. Collect any water that escapes so

that it does not drip on the blower electronics

and damage them. Small amounts of air that

may remain will be purged by the internal pump.

Tighten screw after purging.

It is helpful, for air removal, to manually open

the lever on the anti-condense valve. The “manual

operation” lever located on the top of the valve

operator requires moderate pressure to latch the valve

open and then again to unlatch it and allow it to close.

4. Purge all lines by opening vents.

5. Close gas shutoff valve located above gas valve.

6. Turn on 120 volt power, the display will initially

display [---] for five seconds before displaying

[

OFF].

7. If the temperature sensor detects a temperature

below 39°F (4°C) it will display [

ICE]. The

appliance will then be in its Low Temperature

Mode. The Endurance will call for the pump

to run for 5 minutes, or until the discharge

temperature reaches 45°F (7°C). When the

internal zone valve is manually opened, the

water will be allowed to be pumped to the space

heating system, if the system zones are also open.

This is a good time to ensure that the system is

fully discharged of all air and the water charge

pressure is correct.)

8. If the display remains at [

OFF], press the on/

off button on the boiler control. The Endurance

will respond to any calls for heat it has (DHW,

tank charge, or space heating). The appliance

will attempt to ignite three times after which it

will lock out and display [

LO]. The fan and the

pump will then stop. Ensure that the system is

fully discharged of all air and the water charge

pressure is correct.

9. Turn the main electrical supply off.

10. Manually reset the internal zone valve to its

normal position.

11. System is now ready for operation.

7.3 Firing Burner

1. Be sure the system has been filled properly and is

leak tight.

2. Open gas shutoff valve.

3. Turn on main electrical switch.

4. If the temperature sensor detects a temperature

below 39°F (4°C) it will display [ICE]. The

appliance will then be in its Low Temperature

Mode.

5. If the display shows “OFF”, press the on/

off button on the front upper left of the boiler

control.

6. If the boiler had been locked out, the reset button

on top of the Endurance will need to be pressed.

7. When there is a call for heat, the pump and

the blower will start, the display will show the

supply temperature. The appliance will attempt

to ignite three times, if ignition is not successful,

the appliance will lock out and display “LO”.

Ignition reset is done by pressing the reset button

on top of the control panel. Endurance will

continue to operate until the 20 gallon transfer

tank is up to temperature.

8. Turn on a hot water tap. This puts the appliance

in the DHW mode.

Caution

Should any pronounced odor of gas be

detected, or if the gas burner does not appear

to be functioning in a normal manner, close

main shutoff valve, do not shut off switch, and

contact your heating contractor, gas company,

or factory representative

You MUST check flame monitoring control

(ignition system safety shut-off device).
9. Close gas shutoff valve with burner operating.
10. The gas valve status light will go out, and

immediately a new trial for ignition will begin.

The burner will not relight, because the gas is off.

The control will make two more attempts to light

the burner. Ignition will not occur, as the gas is

off. The boiler will lockout, and the display will

show “LO” after the gas valve has closed on the

third ignition attempt. The ignition control LED

will show a three-flash sequence.

11. Open gas shutoff valve. Press reset button on the

top of the control panel. The ignition sequence

will start again and the burner will start. The

appliance will return to its previous mode of

operation.