LAARS EBP 175 MBTU/h - Installation, Operation and Maintenance Instructions User Manual

Page 35

Advertising
background image

Endurance

Page 35

Natural Gas

LP Gas

CO2

9.0 to 9.6%

9.7 to 10.1%

O2

4.5 to 5.0%

4.5 to 5.0%

Offset

-0.01 to -0.10 in. w.c.

-0.01 to -0.10 in. w.c.

Table 5. Combustion Parameters.

SECTION 11.

Symptom Evaluations

11.1 Delayed ignition

Possible Causes

a. High lockup pressure (LP boilers) - occurs on

start-up.

b. Gas valve regulation problem - occurs on start-up.

c. Incorrect gas orifice (Natural gas orifice in an LP

boiler) - occurs on start up

d. Defective burner - occurs on startup or at burner

shutdown.

High lock up pressure is the most common cause

of delayed ignitions on LP fueled boilers. It may result

from an improper second stage regulator selection or

from a faulty regulator.

Lock up can be detected by measuring the gas

supply pressure to the boiler at the inlet pressure tap

on the gas valve. The gas supply to the boiler must be

shut off before making this connection. Use a water

manometer or pressure gauge with a scale reading of

at least 25 in. w.c. or 15 oz/in

2

. Loosen the screw in

the gas valve pressure port one full turn and install a

hose from the pressure gauge over the pressure port.

Turn on the gas supply. The ENDURANCE boiler is

designed to operate with supply pressures of 4-13 in.

w.c. (2.3 - 7.5 oz/ in²). If the supply pressure exceeds

13 in. w. c. (7.5 oz/ in²) with the boiler not operating

it is possible that this may be the cause of delayed

ignitions and the pressure must be reset to ~ 9 in. w.c.

(5.2 oz/ in²). Restart the boiler and then switch it off

again. Lock up pressures must be measured when the

boiler is not operating and preferably immediately

after boiler shutdown. If the gas pressure again

exceeds the allowable values, correct the lock up

problem.

Gas valve regulation problems can also cause

delayed ignitions. See “Gas valve calibration”.

Incorrect gas orifice – Check orifice size.

A defective burner can cause a delayed ignition

during operation or at shutdown. If the gas supply

pressure is proper the gas valve is functioning properly

and the gas orifice is correct, the burner should be

inspected. To inspect it, remove the blower. The burner

is retained by the blower and it will drop out of the

bottom of the chamber when the blower is removed.

There should be no distortion or perforations in

the burner other than the punched holes. Replace if

indicated.

11.2 Short Cycling

Possible causes

a. Anti-condensing valve not opening.

b. T-T wires cross connected (jumped) – improper

installation

c. Leakage of flue products into the combustion

air stream – Direct Vent Installations only, see

Section 9.2.3

, Resolving Lockouts.

11.3 Noisy Operation

There are two principal sources of noisy

operation:

a. Combustion - high pitched noise - whistle or

hoot.

b. Boiling (kettling) - lower frequency noise which

varies with temperature - moan.

Many times it is difficult to determine the source

of the noise or if it is combustion related or boiling

related. Combustion noises always have the same

frequency; however, their volume may change from

the time that the burner first fires to the time that

it shuts off. A boiling noise is identified by rapidly

raising or lowering the system water pressure while

the noise is present. A change in the pitch or intensity

of the noise indicates a boiling problem.

Combustion noise occurs at any boiler discharge

temperature and is heard the loudest at the flue outlet

(especially on units that are sidewall vented). There

are two basic causes for the noise, rich mixture (high

CO

2

or low O

2

) or cross contamination. The mixture

is determined by measuring the percent O

2

or CO

2

in

the flue products. O

2

readings lower than 4½% or CO

2

readings higher than 9¼% (natural gas) and 10.8%

(LP) will often cause combustion related noise. The

rich mixture could be caused by the mis-calibration of

the gas valve (offset adjustment) or by the gas orifice

size. To eliminate the noise; first, check the gas valve

calibration. If it is correct, install a smaller gas orifice

so that the O

2

will rise above 4½% or the CO

2

will

drop to 8½% (natural) or 9½% (LP).

The CO

2

& O

2

readings may be influenced by

cross contamination. Suspect cross contamination if

the noise returns when the front panel is replaced.

Boiling (kettling) may occur at boiler discharge

temperatures from 170°F to 210°F. The temperature

at which it starts will vary from one installation to

another. The primary cause of the problem is poor heat

transfer on the inside of the boiler coil. This may be

caused by foaming due to excessive concentration of

antifreeze in the system or by scaling from the boiler

water due to hardness of make up water.

Plumbing antifreezes should never be used in a

boiler system. Only boiler antifreezes, with effective

Advertising
This manual is related to the following products: