Cascading multiple boilers, continued, Dhw set point using lead lag (master boiler), Enable the master control function – LAARS NeoTherm NTV (Sizes 080–850 MBTU/h) - Start Up Guide User Manual

Page 10

Advertising
background image

Page 10

LAARS Heating Systems

Cascading multiple boilers, continued


DHW set point using Lead Lag (Master Boiler)


Navigation

Home screen, press “I” Info/Install button

Scroll to highlight “Advanced Setup”, press OK

Highlight “DHW Configure”, press OK

DHW setpoint will be highlighted, press OK

Adjust setpoint, Press OK

Enable the Master control function

The Master control should be enabled from the factory. Check to confirm this function is enabled.

Navigation

Home screen, press “I” Info/Install button

Scroll to “Advanced Set Up”, press OK

Scroll to highlight “Lead Lag Configuration”, press OK

“Lead Lag Master Configure” will be highlighted, press OK

“Master enable” should be highlighted, press OK

Confirm that this function is enabled. If not highlight “Enable”, then press OK

Enable the Slave function on the Master control

When cascading boilers, the Slave function must be turned on. The is done on all of the controls,

including the Master control.

Navigation

Home screen, press “I” Info/Install button

Scroll to “Advanced Set Up”, press OK

Scroll down to highlight “Lead Lag Configure”, press OK

Use the Down button to highlight “Lead Lag Slave Configure”, press OK.

Press OK to “Enable” the Slave function

Use the Down button to highlight “Enable via SOLA master”, press OK