Single Boiler Set Up



Note:

When installing a single boiler, the system sensor supplied with the boiler is not needed. The

system sensor will be needed when cascading multiple boilers together.

The Outdoor sensor supplied with the boiler must be installed. If not, the alarm light on the SOLA

control will be on and the alarm contacts will close.

Single Boiler CH Set Point

Navigation

Home screen Press “I” Info/Install

“Quick Start” should be highlighted, press OK.

CH Setpoint should be highlighted, press OK.

Using the arrows and OK button, adjust the set point. (see the bottom of page 5).

After pressing the round OK button to confirm a set point, the display will go back to the “Quick

Start” screen. You can now select and adjust other parameters from this screen. The screen will time

out after 8 minutes of no activity, and return back to the Home Screen.

Single boiler DHW Set Point

Navigation

Home screen, Press “I” Info/Install

“Quick Start” should be highlighted, press OK

Use the Down arrow button to Highlight “DHW set point”, press OK.

Using the arrow and OK button, adjust the set point. (see the bottom of page 5).

Press OK

Single boiler Outdoor reset

Note:

The Outdoor reset is Enabled from the factory. (No further steps needed).