Cascading multiple boilers, continued

Combustion Set Up


High Fire

Navigation

Home screen

Press “I” Info/Install button

Scroll to highlight “Test”, press OK

“Forced Rate” will be highlighted, press OK

If the screen prompts you to Log in, press OK and Log in

Note: The boiler must be running to start High or Low fire test

“Set High Fire” will be highlighted, press OK

Scroll down to “Start Test” press OK

You will now have five minutes to complete the High fire CO2 adjustments

Low Fire

Navigation

From the “Forced Rate” screen, highlight the option for “Set Low Fire”, press OK

Scroll down to “Start Test”, press OK. Complete Low Fire CO2 adjustments.




CO2 Adjustment Range

Gas Type

High Fire CO2

Low Fire CO2

Natural

9.0 to 9.8 %

0.5% lower than High Fire

Propane

10.0 to 10.8 % 0.5% lower than High Fire