Table 14 — Individual Component Ratings

POWER SOURCE

ITEM

AVERAGE kW

DESIGN CENTER

VOLTAGE

SUPPLY

V-PH-HZ

FLA

LRA

1*

(17EX Only)

Seal Leakage

Pump

0.23

115

115-1-50/60

4.78

21.7

Motor Space

Heater

0.50

115

115-1-50/60

4.35

4.35

1†

Control Module

and Actuator

0.40

115

115-1-60

3.50

115-1-50

Oil Sump Heater

1.00

115

115-1-60

8.70

115-1-50

2†

Oil Pump

1.35

220

200/240-3-60

4.32

24.5

1.30

430

380/480-3-60

2.15

12.2

1.37

563

507/619-3-60

2.13

25.0

1.49

230

220/240-3-50

4.83

28.0

1.49

393

346/440-3-50

2.59

12.2

1**

Hot Gas

Bypass

0.20

115

115-1-50/60

2.00

4.75

3**

(Optional)

Pumpout

Compressor

3.41

204

200/208-3-60

10.90

63.5

230

220/240-3-60

9.50

57.5

460

440/480-3-60

4.70

28.8

575

550/600-3-60

3.80

23.0

400

380/415-3-50

4.70

28.8

LEGEND

FLA — Full Load Amps
LRA — Locked Rotor Amps

*Available for 17EX machines only.

†Available for 17/19EX machines.

**Available as an option on 17/19EX machines.

NOTE: The oil pump is powered through a field wiring terminal into
the power panel. Power to the controls and oil heater via the power
panel must be on circuits that can provide continuous service when
the compressor starter is disconnected.