Carrier Centrifugal Liquid Chiller 19EX User Manual
Page 22

Table 14 — Individual Component Ratings
POWER SOURCE
ITEM
AVERAGE kW
DESIGN CENTER
VOLTAGE
SUPPLY
V-PH-HZ
FLA
LRA
1*
(17EX Only)
Seal Leakage
Pump
0.23
115
115-1-50/60
4.78
21.7
Motor Space
Heater
0.50
115
115-1-50/60
4.35
4.35
1†
Control Module
and Actuator
0.40
115
115-1-60
3.50
—
115-1-50
Oil Sump Heater
1.00
115
115-1-60
8.70
—
115-1-50
2†
Oil Pump
1.35
220
200/240-3-60
4.32
24.5
1.30
430
380/480-3-60
2.15
12.2
1.37
563
507/619-3-60
2.13
25.0
1.49
230
220/240-3-50
4.83
28.0
1.49
393
346/440-3-50
2.59
12.2
1**
Hot Gas
Bypass
0.20
115
115-1-50/60
2.00
4.75
3**
(Optional)
Pumpout
Compressor
3.41
204
200/208-3-60
10.90
63.5
230
220/240-3-60
9.50
57.5
460
440/480-3-60
4.70
28.8
575
550/600-3-60
3.80
23.0
400
380/415-3-50
4.70
28.8
LEGEND
FLA — Full Load Amps
LRA — Locked Rotor Amps
*Available for 17EX machines only.
†Available for 17/19EX machines.
**Available as an option on 17/19EX machines.
NOTE: The oil pump is powered through a field wiring terminal into
the power panel. Power to the controls and oil heater via the power
panel must be on circuits that can provide continuous service when
the compressor starter is disconnected.
22