Install Field Insulation

Protect insulation from weld heat damage and weld splat-
ter. Cover with wet canvas cover during water piping
installation.

When installing insulation at the job site, insulate the fol-

lowing components (see Fig. 24 and Table 15):
• compressor motor
• cooler shell
• cooler tube sheets
• suction piping
• motor cooling drain
• oil cooler refrigerant side tubing
• utility vessel (low side)

Additional insulation of condenser and compressor com-

ponents and lines may be necessary to prevent condensation
on these components.
NOTE: Carrier does not provide waterbox insulation. Insu-
lation of the waterbox covers must be field supplied at the
jobsite. When insulating the waterbox covers, allow enough
room for removal of the waterbox covers during servicing.

FACTORY INSULATION (OPTIONAL) — Optional
factory insulation is available for the evaporator shell and
tube sheets, suction pipe, compressor motors, and refriger-
ant drain line(s). Insulation applied at the factory is

3

4

in.

(19.0 mm) thick and has a thermal conductivity K value of

Btu

in.

W

0.28

(0.0404

°C). Insulation conforms

hr

ft

2

°F

m

with UL Standard 94, Classification 94 HBF.

Table 15 — Insulation Requirements

Sheet Foam Insulation

COMPONENT

ft

2

m

2

Cooler Shell (Sizes 31-33)

254

23.6

Cooler Shell (Sizes 41-44)

306

28.4

Cooler Shell (Sizes 45-48)

374

34.7

Economizer Low Side Float Chamber

48

4.5

Economizer Main Shell (with cooler sizes 31-44)

85

7.9

Economizer Main Shell (with cooler sizes 45-48)

115

10.1

Suction Line

25

2.3

Cooler Marine Waterbox (1 or 3 pass, with

frame-3 coolers)

126

11.7

Cooler Marine Waterbox (2 pass, with

frame-3 coolers)

100

9.3

Cooler Marine Waterbox (1 or 3 pass, with

frame-4 coolers)

158

14.7

Cooler Marine Waterbox (2 pass, with

frame-4 coolers)

123

11.4

Cooler NIH Waterbox (with frame-3 coolers)

74

6.9

Cooler NIH Waterbox (with frame-4 coolers)

88

8.2

Main Motor Shell (with −51 through −89

compressors)

27

2.5

Main Motor Shell (with 421 through 469 compressors)

27

2.5

Main Motor Shell (with 531 through 599 compressors)

41

3.8

Foam Tubing Insulation

TYPE

Ft

m

1

1

8

؆

Foam Tubing

9

2.7

1

5

8

؆

Foam Tubing

2

0.6

2

؆

Foam Tubing

9

2.7

5

؆

Foam Tubing

14

4.3

NOTES:
1. Cooler

value

includes

marine

waterbox

on

one

end

(even-pass

arrangement).

2. Values are approximate.
3. Thermal insulation is available as a factory-installed option. Waterbox in-

sulation must be field supplied.