5.2 Status Register

The status register contains alarms and system status flags that can be monitored by the host processor.

Alarms thresholds can be set through the corresponding registers.

Sticky Bits Register
The sticky bit register at address 0xF3 (CLI) and 0x3CC (SPI) allows the user to set the mode of the

status register bit. Each bit can individually be programmed to clear automatically once an alarm

condition no longer exists or to holds its status until cleared by writing to the status register.

Status Register

CLI Address

0xF5

SPI Address

0x3D4

Bit

Description / Comment

1, 0

Not Used

2

Minimum Temperature Alarm (Under Temperature)

3

Maximum Temperature Alarm. (Over Temperature)

4

UnderCurrent phase C

5

UnderCurrent phase B

6

UnderCurrent phase A

7

OverCurrent phase C

8

OverCurrent phase B

9

OverCurrent phase A

10

Voltage Imbalance phase C

11

Voltage Imbalance phase B

12

Voltage Imbalance phase A

13

Under-Voltage phase C

14

Under-Voltage phase B

15

Under-Voltage phase A

16

Over-Voltage phase C

17

Over-Voltage phase B

18

Over-Voltage phase A

20

Power Factor phase C

21

Power Factor phase B

22

Power Factor phase A

23 -30

Not Used

31

Command Done