Power Supply and Wiring —

Check the unit data

plate to ensure that available power supply matches electri-
cal characteristics of the unit. Provide a disconnect switch of
size required to provide adequate fan motor starting current.
See Tables 4 - 6 for unit electrical data.

Install disconnect switch and power wiring in accordance

with all applicable local codes. See Fig. 12-14 and the unit
label diagram. For units with motor sizes less than 5 Hp
(3.7 kW), connect power wiring to unit with no. 10 ring ter-
minal. For units with motor sizes of 5 Hp (3.7 kW) or more,
connect power wiring with

1

4

-in. ring terminal.

The 40RM, 40RMQ and 40RMS size 007-016 units (ex-

cept 40RM016 with YC or WD option) that have motors wired
for 460-v, 3-ph, 60 Hz operation can be field-converted to

230-v, 3-ph, 60 Hz operation. Rewire the motor according to
the diagram plate on the motor. After reconfiguring the mo-
tor, place the sticker specifying 230-v operation (supplied in
installation packet) over the 460-v sticker on the units cor-
ner post.

Fan motors are factory installed on all units. Indoor-fan

contactors are located in the fan contactor box behind the
side access panel (see Fig. 12 and 13). Wire the thermostat
to the 24-v control circuit terminal block located in the side
of the fan contactor control box, according to Fig. 14 or the
unit label diagram. If the air handler is part of a split system,
complete the wiring from the condensing unit to the ther-
mostat shown in Fig. 14.

FAN
CONTACTOR
BOX

CONDENSATE
DRAIN
CONNECTION
(HORIZONTAL)

WIRING
ACCESS

COIL

REFRIGERANT/
CHILLED WATER
PIPING ACCESS

CONDENSATE
DRAIN
CONNECTION
(VERTICAL)

MOTOR
AND DRIVE

FAN SCROLL

FILTER
ELEMENTS

FILTER
RETAINER
CLIP

TXV BULB
ACCESS

FAN DRIVE
PULLEY

TXV — Thermostatic Expansion Valve

Fig. 12 — Wiring and Service Access

(Side Panel Removed)

23

22

21

13

12

11

105

°

C 600V RJ A

W

FAN
CONTACTOR

24V
TERMINAL
BLOCK

POWER
WIRING
KNOCKOUT

Fig. 13 — Fan Contactor Box and Terminal Block

(Cover Removed) (Typical)