background image

Table 6 — Fan Contactor Coil Data

UNIT

40RM, 40RMQ

40RMS

VOLTAGE

(vac)

MAXIMUM

HOLDING

VA

007-034

24

10

Connecting Ductwork —

Refer to the Carrier Sys-

tem Design Manual for the recommended design and layout
of ductwork. Figure 15 shows recommended duct connec-
tion to units with 2 fans.
DISCHARGE CONNECTIONS — Duct flanges are factory
supplied; they are shipped inside the unit attached to the hair-
pin end of the coil tube sheet for field installation. Using the
existing screws, install the duct flanges on the unit’s fan deck.
Each fan discharge requires 2 flanges; each flange must be
bent in the middle to conform to the discharge opening. See
Fig. 16. After flanges are installed, connect them to the sup-
ply duct using a canvas connection to prevent vibration. It is
important that this connection be properly fabricated to pre-
vent high air friction losses and air noise.
RETURN CONNECTION — When using return-air duct-
work, route return-air duct to the unit’s return air inlet near
the filter rack, using a canvas connection to prevent trans-
mission of unit vibration. If the duct blocks off the unit’s
access panel, provide a slip joint in the ductwork to permit
removal for servicing.
OUTDOOR-AIR INLET CONNECTION — Connect outdoor-
air inlet to field-installed accessory economizer. Refer to econo-
mizer Installation Instructions.

Return-Air Filters —

Type and size of filters are

shown in Tables 1A-1F and are factory-supplied and in-
stalled. In all units with 2 fans, a filter replacement tool (hook)
is shipped inside the unit for field use when replacing filters.
See the Service section for instructions on filter element
replacement.

Fig. 14 — Unit Wiring

LEGEND

CB

Circuit Breaker

HC

Heating Contactor

HTR

Electric Heater

IFC

Indoor-Fan Contactor

IFM

Indoor-Fan Motor

NEC

National Electrical Code

TB

Terminal Block

T’STAT — Thermostat

Factory Wiring
Field Control Wiring

NOTE: Use copper conductors only.