Legend and Notes for Tables 10C and 10D

LEGEND

ESP — External Static Pressure

NOTES:
1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and

034; 20 r/s for all other sizes.

2. Fan performance is based on deductions for wet coil, clean 51-mm

filters, and unit casing. See right for factory-supplied filter pres-
sure drop.

3. Refer to fan motor and drive tables for additional data.

Factory-Supplied Filter Pressure Drop — SI

UNIT

AIRFLOW

(L/s)

PRESSURE DROP

(Pa)

40RM

007

850

1150
1450

13
20
28

40RM

40RMQ

40RMS

008

1000
1400
1800

17
27
38

40RMS

010

1200
1600
2000

21
32
45

40RM

40RMQ

40RMS

012

1450
1900
2350

28
42
56

40RM

40RMS

014

1750
2350
2950

15
24
33

40RM

40RMQ

40RMS

016

2100
2800
3500

20
30
42

40RM

40RMS

024

2900
3800
4700

32
47
64

40RM

40RMS

028

3500
4700
5900

36
55
76

40RM

40RMS

034

4250
5650
7050

47
71
98

Replacing Filters —

Filters can be removed and in-

stalled from either side of the unit. Install new filters in units
that have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip.
3. Remove old filters by tilting them and lifting them out of

the filter track. See Fig. 12 and 22.

4. Reverse the procedure to install new filters.

To install new filters in larger units that have 2 fans, fol-

low the preceding steps, but use the factory-supplied
filter hook to slide filters within reach for removal. The
filter hook is shipped inside the unit in the baserail.

Do not operate unit without air filters.

Fig. 22 — Filter Removal/Replacement