Table 9C — High-Static Drive Data, 60 Hz — English

UNIT

40RM

007

40RM

40RMQ

40RMS

008

40RMS

010

40RM

40RMQ

40RMS

012

40RM

40RMS

014

40RM

40RMQ

40RMS

016

40RM

40RMS

024

40RM

40RMS

028

40RM

40RMS

034

MOTOR DRIVE

Motor Pulley Pitch Diameter

(in.)

3.4-4.4

3.4-4.4

3.4-4.4

3.4-4.4

3.7-4.7

4.3-5.3

4.3-5.3

4.3-5.3

4.3-5.3

Pulley Factory Setting

Full Turns Open

2.5

2.5

2.5

2.5

3.0

3.0

3.0

3.0

3.0

FAN DRIVE

Pulley Pitch Dia (in.)

7.0

6.0*

6.0

6.0

7.4

7.9

7.4

8.6

8.6

Pulley Bore (in.)

1

1

1

1

1

7

16

1

7

16

1

7

16

1

15

16

1

15

16

Belt No. — Section

1—A

1—A

1—A

1—A

1—B

1—B

2—B

2—B

2—B

Belt Pitch (in.)

41.3

37.3

37.3

37.3

39.8

39.8

36.8

37.8

37.8

FAN SPEEDS (rpm)

Factory Setting

961

1121

1121

1121

979

1060

1118

1024

1024

Range

838-

1084

978-

1200*†

978-

1200†

978-

1200†

873-

1096

950-

1171

1014-

1200†

873-

1075

873-

1075

Max Allowable Speed (rpm)

1200

1200

1200

1200

1200

1200

1200

Change per

1

2

Turn of

Moveable Motor Pulley
Flange

24.6

28.7

28.7

28.7

19.4

18.4

19.4

16.7

16.7

MAX FULL TURNS FROM

CLOSED POSITION

5

5

5

5

6

6

6

6

6

SHAFTS CENTER DISTANCE

(in.)

10.44-
12.32

10.44-
12.32

10.44-
12.32

10.44-
12.32

10.44-

12.32**

9.16-

10.99

8.16-

10.02

6.67-
9.43

6.67-
9.43

*Valves for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.

and resulting fan speed is 837-1096 rpm.

†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT

exceed 1200 rpm.

**575-v unit has a center distance of 9.16-10.99.

Table 9D — Standard Drive Data, 50 Hz — English

UNIT

40RM

007

40RM

40RMQ

40RMS

008

40RMS

010

40RM

40RMQ

40RMS

012

40RM

40RMS

014

40RM

40RMQ

40RMS

016

40RM

40RMS

024

40RM

40RMS

028

40RM

40RMS

034

MOTOR DRIVE

Motor Pulley Pitch Diameter
(in.)

2.4-3.4

2.8-3.8

2.8-3.8

3.4-4.4

3.4-4.4

3.4-4.4

4.3-5.3

4.3-5.3

4.3-5.3

Pulley Factory Setting

Full Turns Open

2.5

2.5

2.5

2.5

2.5

2.5

3.0

3.0

3.0

FAN DRIVE

Pulley Pitch Dia (in.)

8.0

8.0

8.0

8.0

9.0

9.0

8.6

11.0

11.0

Pulley Bore (in.)

1

1

1

1

1

7

16

1

7

16

1

7

16

1

15

16

1

15

16

Belt No. — Section

1—A

1—A

1—A

1—A

1—A

1—A

1—B

2—B

2—B

Belt Pitch (in.)

39.3

39.3

39.3

40.3

42.3

42.3

41.8

43.8

43.8

FAN SPEEDS (rpm)

Factory Setting

517

588

588

695

618

618

795

622

622

Range

428-606

499-677

449-677

606-784

538-697

538-697

713-878

557-687

557-687

Max Allowable Speed (rpm)

1200

1200

1200

1200

1200

1200

1200

1100

1100

Change per

1

2

Turn of

Moveable Motor Pulley
Flange

17.8

17.8

17.8

17.8

15.9

15.9

13.8

10.8

10.8

MAX FULL TURNS FROM

CLOSED POSITION

5

5

5

5

5

5

6

6

6

SHAFTS CENTER DISTANCE

(in.)

10.44-
12.32

10.44-
12.32

10.44-
12.32

10.44-
12.32

10.44-
12.32

10.44-
12.32

9.12-

10.99

6.67-
9.43

6.67-
9.43