Compaq Presario 3000 Series User Manual

Page 55

Advertising
background image

Configuration 4-9

Operating Range

Utility Voltage

+20%

- 20%

-35%

Time

V

oltage

Nominal

Extended

Range

Figure 4-6. Utility voltage fluctuation indicating a possible need for
extended range setting

To match the utility voltage, the UPS operating range can be modified in two
ways:

If the utility voltage differs from the currently configured nominal
voltage, but stays within a ±20% band (see Fig 4-5), consider shifting
the nominal voltage parameter selection to match the measured utility
voltage range.

If the utility voltage frequently varies outside the UPS operating range
(see Fig 4-6), consider changing from normal to extended range
(+20% to –35%). This provides more tolerance to brief utility voltage
fluctuations.

To update the nominal voltage and operating range parameters:

1.

Have a qualified electrician monitor utility voltage.

2.

Use the following tables to identify the operating range that most closely
matches requirements:

Advertising