Use the following formula to determine the percent volt-

age imbalance.

% Voltage Imbalance:

max voltage deviation from average voltage

= 100 ×

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance:

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below
the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance
is more than 2%, contact your local electric utility com-
pany immediately.

Unit failure as a result of operation on improper line volt-

age or excessive phase imbalance constitutes abuse and may
cause damage to electrical components. See Tables 2-5 for
unit, electric heater, and 50ME electrical application elec-
trical data.

Each 50ME electric heat unit is fitted with a heating lock-

out circuit (if equipped with optional heat). If any zone mod-
ule is operating on mechanical cooling (compressor is op-
erating), the heating element in each zone module is locked
out and cannot be energized.

On 50ME units, cooling power supply wires and electric

heater power supply wires (if applicable) must be sized ac-
cording to the cooling MCA (Minimum Circuit Amps) val-
ues and heating MCA values shown on unit nameplate and
in Tables 3-5. These wires may be powered by a common
power supply (i.e., a pull-box junction), if desired. The com-
mon power supply wires from the main power source to the
junction must be sized according to the common MCA val-
ues shown in Table 5.
UNIT COMMON FEED MINIMUM CIRCUIT AMPS —
The unit common feed MCA is calculated on the basis of
either: the sum of the cooling MCA plus

1

2

heating MCA on

units with 2 heating elements per zone module (or

2

3

heat-

ing MCA on units with 3 heating elements per zone module)
or the sum of the evaporator fan motor full load amps, per
NEC, plus the full heating MCA, whichever is larger. Field
wiring must conform to NEC limitations for Type T wire.

Table 2 — Unit 48MA Electrical Data

UNIT

48MA

Voltage

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMP

NO. 1

COMP

NO. 2

OFM

FLA

COMBUSTION

FAN MOTOR

IFM

POWER

SUPPLY

Min

Max

RLA

LRA

RLA

LRA

No. 1

No. 2

No. 3

FLA

Hp

FLA

MCA

MOCP

016

208/230

187

254

63.6

266

6.2

6.6

1.8

5

16.2

109.6

125

460

414

508

28.6

120

3.0

6.6

49.8

60

575

518

632

22.8

96

2.4

5.6

39.8

45

024

208/230

187

254

44.4

170

44.4

170

6.2

6.6

1.8

7.5

24.2

137.5

150

460

414

508

19.9

77

19.9

77

3.0

11.0

62.2

70

575

518

632

15.7

62

15.7

62

2.4

9.0

49.4

60

028

208/230

187

254

63.6

266

44.4

170

6.2

6.6

1.8

10

30.8

168.1

200

460

414

508

28.6

120

19.9

77

3.0

13.0

76.1

90

575

518

632

22.8

96

15.7

62

2.4

10.5

60.4

70

030

208/230

187

254

63.6

266

63.6

266

6.2

6.6

1.8

10

30.8

187.3

200

460

414

508

28.6

120

28.6

120

3.0

13.0

84.5

100

575

518

632

22.8

96

22.8

96

2.4

10.5

67.5

90

034

208/230

187

254

63.6

266

63.6

266

6.2

6.6

6.6

1.8

15

46.2

210.8

225

20

61.0

224.6

250

460

414

508

28.6

120

28.6

120

3.0

3.0

15

21.0

94.5

100

20

26.6

100.5

125

575

518

632

22.8

96

22.8

96

2.4

2.4

15

16.0

75.6

90

20

21.3

80.6

100

040

208/230

187

254

80.0

345

80.0

345

6.2

6.6

6.6

1.8

15

46.2

247.7

300

20

61.0

261.5

300

460

414

508

38.5

150

38.5

150

3.0

3.0

15

21.0

116.7

150

20

27.0

122.7

150

575

518

632

31.4

120

31.4

120

2.4

2.4

15

16.0

95

125

20

21.3

100

125

LEGEND

COMP — Compressor
FLA

Full Load Amps

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

NOTES:
1. Combustion air fan is a 115-1-60 motor on all units.
2. Condenser fan motor no. 1 is a 208/230-1-60 speed control motor

on all units.

11