Gas heat lighting procedure (48ma), Intermittent pilots (48ma) – Carrier 48MA/50ME016-040 User Manual

Page 35

Advertising
background image

The heating thermostat energizes a 115-v solenoid by means

of a gas valve relay and the pilot lights. The main burner
comes on after the pilot is proven.

The safety switches (airflow switches 1 and 2, pilot flame

sensor, door switch, and limit switches) are in series with
the gas valve.

Gas Heat Lighting Procedure (48MA)

1. Purge gas supply line of air. Make sure unit main manual

and zone module gas valves have been off for 5 minutes
before proceeding.

2. Set each zone thermostat to the lowest setting.
3. Turn zone module and main manual gas valves to ON

position, and secure door of burner compartment.

4. Turn on unit main power supply. Set control circuit serv-

ice switch in condensing control box at ON position. Evapo-
rator fan will be energized.

5. Set zone thermostat to call for heat. Pilot will light. The

main burner will come on after the pilot is proven.

NOTE: A time-delay relay will shut unit down in 180 sec-
onds if main manual gas valve is not open.

TO SHUT OFF GAS HEAT — Set control circuit service
switch at OFF position. Shut off unit power supply only if
necessary. Remove heating controls compartment access door.
Shut off main manual gas valves and pilot manual gas valves.

Intermittent Pilots (48MA) —

Pilot flame should be

approximately 1 to 1

1

2

in. high.

ADJUSTMENT
1. Turn system switch to OFF position.
2. If intending to adjust every zone, disconnect main gas

valve wires from terminal W on pilot switches in each
zone.

LEGEND

HA — Heat Anticipator
HU — Humidistat
TC — Thermostat, Cooling
TH — Thermostat, Heating

Screw Terminal

Printed Circuit
Factory Control Wires
Field Wiring

Fig. 30 — Humidistat Connections

LEGEND

CCP

Capacity Control Pressure Switch

DLT

Discharge Line Thermostat

FCPS

Fan Cycling Pressure Switch

FP

Fusible Plug

HGBP — Hot Gas Bypass
HPS

High-Pressure Switch

IFM

Indoor (Evaporator) Fan Motor

LLS

Liquid Line Solenoid

LPS

Low-Pressure Switch

OFM — Outdoor (Condenser) Fan Motor
TXV

Thermostatic Expansion Valve

Hand Valve

Auto. Valve

Capilliary

Fig. 31 — Refrigerant Piping Schematic (10-Zone Unit Shown — 8- and 12-Zone Units Similar)

35

Advertising