Table 3 — Unit 50ME Electrical Data

UNIT

50ME

VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMP

NO. 1

COMP

NO. 2

OFM

FLA

IFM

POWER

SUPPLY

Min

Max

RLA

LRA

RLA

LRA

No. 1

No. 2

No. 3

Hp

FLA

MCA

MOCP

016

208/230

187

254

63.6

266

6.2

6.6

5

16.2

109.6

125

460

414

508

28.6

120

3.0

6.6

49.5

60

575

518

632

22.8

96

2.4

5.6

39.6

45

024

208/230

187

254

44.4

170

44.4

170

6.2

6.6

7.5

24.2

138.0

150

460

414

508

19.9

77

19.9

77

3.0

11.0

61.9

70

575

518

632

15.7

62

15.7

62

2.4

9.0

49.2

60

028

208/230

187

254

63.6

266

44.4

170

6.2

6.6

10

30.8

168.9

200

460

414

508

28.6

120

19.9

77

3.0

13.0

75.8

90

575

518

632

22.8

96

15.7

62

2.4

10.5

60.2

70

030

208/230

187

254

63.6

266

63.6

266

6.2

6.6

10

30.8

188.0

200

460

414

508

28.6

120

28.6

120

3.0

13.0

84.5

100

575

518

632

22.8

96

22.8

96

2.4

10.5

67.3

90

034

208/230

187

254

63.6

266

63.6

266

6.2

6.6

6.6

15

46.0

210.8

225

20

61.0

224.6

250

460

414

508

28.6

120

28.6

120

3.0

3.0

15

19.8

94.5

100

20

26.6

100.5

125

575

518

632

22.8

96

22.8

96

2.4

2.4

15

16.0

75.6

90

20

21.3

80.6

100

040

208/230

187

254

80.0

345

80.0

345

6.2

6.6

6.6

15

46.2

247.7

300

20

61.0

261.5

300

460

414

508

39.3

150

39.3

150

3.0

3.0

15

19.8

118.5

150

20

26.6

124.5

150

575

518

632

31.4

120

31.4

120

2.4

2.4

15

16.0

95

125

20

21.3

100

125

LEGEND

COMP — Compressor
FLA

Full Load Amps

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

NOTE: Condenser fan motor no. 1 is a 208/230-1-60 speed control
motor on all units.

Table 4 — Electric Resistance Heater Data

UNIT

50ME

NOMINAL
VOLTAGE

(3 Ph, 60 Hz)

ELECTRIC

HEAT kW

(Unit Total)

HEATING ELEMENTS

PER ZONE MODULE

FLA PER

HEATING ELEMENT

MCA

(Each Circuit)

MOCP

(Each Circuit)

016,024

208/230

43/ 53
57/ 70
87/106

2
2
3

13.0/14.4
17.3/19.2
17.3/19.2

150/166
200/221
150/166

175/175
225/225
175/175

460

53
70

106

2
2
3

7.2
9.6
9.6

83

111

166

90

125
175

575

106

3

7.7

133

150

028,030

208/230

54/ 66
72/ 88

108/132

2
2
3

13.0/14.4
17.3/19.2
17.3/19.2

188/207
250/276
188/207

200/225
275/300
200/225

460

66
88

132

2
2
3

7.2
9.6
9.6

103
138
207

110

150
225

575

132

3

7.7

166

175

034,040

208/230

65/ 79
87/106

129/158

2
2
3

13.0/14.4
17.3/19.2
17.3/19.2

225/249
150/165
225/249

250/250
175/175
250/250

460

79

106
158

2
2
3

7.2
9.6
9.6

124
166
249

125
175
250

575

158

3

7.7

199

200

LEGEND

FLA

Full Load Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NOTES:
1. Heaters are rated at 230 v, 460 v, and 575 v.
2. Terminal boards provided for heater power wire connections are

suitable for use with copper or aluminum wire.

12