Caution – Reznor RDH with 1-stage gas control or 2-stage gas control Gas Conversion Kit Instructions User Manual

Page 5

Advertising
background image

Form CP-PREEVA-GC, P/N 212063 R7, Page 5

5. Turn on the electricity and the gas. Relight, following the instructions on the

heater. Check for gas leaks using a commercial leak detecting fluid or a rich soap

and water solution. Leaks are indicated by the presence of bubbles. Check all

connections. If a leak cannot be stopped by tightening, replace the part.

6. Adjust the manifold pressure. Follow these requirements and instructions to

adjust manifold gas pressure.

1) The correct pressure adjustment depends on the area of the country in terms of

elevation. Refer to

TABLE 2 and determine the required valve outlet pressure

for the elevation where the heater will be operating. If you don’t know the

elevation, check with your local gas company.

2) Locate the 1/8” output pressure tap on the valve (See

FIGURE 4). Turn the

knob or switch on the top of the valve to “OFF”. Connect a manometer to the

1/8” pipe outlet pressure tap in the valve. Use a water column manometer that

is readable to the nearest tenth of an inch.

FIGURE 4 - Top View

of Valves identifying

Pressure Taps and

Adjustment Screws

Single-Stage

Valve

(two styles)

1/8” Outlet

Pressure Tap

Adjust Outlet

Pressure

Inlet

Pressure Tap

Two-Stage Valve

Adjust High

Fire Outlet

Pressure

Adjust Low

Fire Outlet

Pressure

Inlet

Pressure

Tap

1/8” Outlet

Pressure Tap

1/8” Outlet

Pressure Tap

Inlet Pressure Tap

Adjust Outlet Pressure

Applies to Model PDH, SDH, and RDH with Gas Controls listed

Altitude

Normal Manifold Pressure (Single-

Stage and Two-Stage High Fire) -

Applies to Options AG1, AG2, AG3,

AG15, AG16

2-Stage Low-Fire Manifold

Pressure - Applies to Options

AG2, AG3, AG15, AG16

FEET

METERS

NATURAL

PROPANE

NATURAL

PROPANE

Manifold Pressure Settings (inches w.c.) by Altitude for Installation in the UNITED STATES

0 - 2000

0 - 610

3.5

10.0

1.8

5.0

2001 - 3000 611 - 915

3.1

8.8

1.6

4.4

3001 - 4000 916 - 1220

3.0

8.5

1.5

4.2

4001- 5000 1221 - 1525

2.8

8.1

1.5

4.1

5001 - 6000 1526 - 1830

2.7

7.7

1.4

3.9

6001 - 7000 1831 - 2135

2.6

7.4

1.3

3.7

7001 - 8000 2136 - 2440

2.5

7.1

1.3

3.5

8001 - 9000 2441 - 2745

2.4

6.7

1.2

3.4

Manifold Pressure Settings (inches w.c.) by Altitude for Installation in CANADA

0 - 2000

0 - 610

3.5

10.0

1.8

5.0

2001 - 4500 611 - 1373

2.8

8.1

1.5

4.1

TABLE 2 - Valve Outlet

Pressure Settings by

Elevation, Control

Option, and Fuel Type

3)

Single-Stage and Two-Stage High Fire - Turn the knob or switch on the top

of the valve to “ON”. Remove the cap from the pressure adjusting screw and

adjust the gas train pressure to the pressure selected from the table. Adjust

pressure by turning the regulator screw IN (clockwise) to increase pressure or

OUT (counterclockwise) to decrease pressure.

Two-Stage Low Fire - Disconnect the wire from the “HI” terminal on the gas

valve and check the low fire pressure. Turn the regulator screw to adjust

the low fire outlet pressure to the “Low Fire” pressure listed in the table.

Re-connect the wire to the gas valve.

CAUTION

DO NOT bottom

out the gas

valve regulator

adjusting screw.

This can result

in unregulated

manifold pressure

causing excess

overfire and heat

exchanger failure.

4) Turn up the thermostat. (NOTE: On Model SDH, depress and hold the door

safety switch.) Cycle the burner once or twice to properly seat the adjustment

spring in the valve.

Advertising