0514 (Serial No. Date Code BNE) Form CP-PREEVA-GC (Version A.1)

®

High Altitude

Capacity Changes

2-Stage Minimum

Input NOTE:

“2-Stage Minimum

Input” column” is

70% and applies to

units with 2-stage

control system

Options AG2, AG3,

AG15, and AG16

ALTITUDE

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

Feet

Meters

Size 75

Size 100

Size 125

0-2000

0-610

75,000

60,750

52,500

100,000

81,000

70,000

125,000

101,250

87,500

2001-3000

611-915

70,500

57,105

49,350

94,000

76,140

65,800

117,500

95,175

82,250

3001-4000

916-1220

69,000

55,890

48,300

92,000

74,520

64,400

115,000

93,150

80,500

4001-5000

1221-1525

67,500

54,675

47,250

90,000

72,900

63,000

112,500

91,125

78,750

5001-6000

1526-1830

66,000

53,460

46,200

88,000

71,280

61,600

110,000

89,100

77,000

6001-7000

1831-2135

64,500

52,245

45,150

86,000

69,660

60,200

107,500

87,075

75,250

7001-8000

2136-2440

63,000

51,030

44,100

84,000

68,040

58,800

105,000

85,050

73,500

8001-9000

2441-2745

61,500

49,815

43,050

82,000

66,420

57,400

102,500

83,025

71,750

Feet

Meters

Size 150

Size 175

Size 200

0-2000

0-610

150,000

121,500

105,000

175,000

141,750

122,500

200,000

162,000

140,000

2001-3000

611-915

141,000

114,210

98,700

164,500

133,245

115,150

188,000

152,280

131,600

3001-4000

916-1220

138,000

111,780

96,600

161,000

130,410

112,700

184,000

149,040

128,800

4001-5000

1221-1525

135,000

109,350

94,500

157,500

127,575

110,250

180,000

145,800

126,000

5001-6000

1526-1830

132,000

106,920

92,400

154,000

124,740

107,800

176,000

142,560

123,200

6001-7000

1831-2135

129,000

104,490

90,300

150,500

121,905

105,350

172,000

139,320

120,400

7001-8000

2136-2440

126,000

102,060

88,200

147,000

119,070

102,900

168,000

136,080

117,600

8001-9000

2441-2745

123,000

99,630

86,100

143,500

116,235

100,450

164,000

132,840

114,800

Feet

Meters

Size 225

Size 250

Size 300

0-2000

0-610

225,000

182,250

157,500

250,000

202,500

175,000

300,000

243,000

210,000

2001-3000

611-915

211,500

171,315

148,050

235,000

190,350

164,500

282,000

228,420

197,400

3001-4000

916-1220

207,000

167,670

144,900

230,000

186,300

161,000

276,000

223,560

193,200

4001-5000

1221-1525

202,500

164,025

141,750

225,000

182,250

157,500

270,000

218,700

189,000

5001-6000

1526-1830

198,000

160,380

138,600

220,000

178,200

154,000

264,000

213,840

184,800

6001-7000

1831-2135

193,500

156,735

135,450

215,000

174,150

150,500

258,000

208,980

180,600

7001-8000

2136-2440

189,000

153,090

132,300

210,000

170,100

147,000

252,000

204,120

176,400

8001-9000

2441-2745

184,500

149,445

129,150

205,000

166,050

143,500

246,000

199,260

172,200

Feet

Meters

Size 350

Size 400A

0-2000

0-610

350,000

283,500

245,000

400,000

324,000

280,000

2001-3000

611-915

329,000

266,490

230,300

376,000

304,560

263,200

3001-4000

916-1220

322,000

260,820

225,400

368,000

298,080

257,600

4001-5000

1221-1525

315,000

255,150

220,500

360,000

291,600

252,000

5001-6000

1526-1830

308,000

249,480

215,600

352,000

285,120

246,400

6001-7000

1831-2135

301,000

243,810

210,700

344,000

278,640

240,800

7001-8000

2136-2440

294,000

238,140

205,800

336,000

272,160

235,200

8001-9000

2441-2745

287,000

232,470

200,900

328,000

265,680

229,600

ALTITUDE

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

Feet

Meters

Size 75

Size 100

Size 125

0-2000

0-610

75,000

60,750

52,500

100,000

81,000

70,000

125,000

101,250

87,500

2001-4500

611-1373

67,500

54,675

47,250

90,000

72,900

63,000

112,500

91,125

78,750

Feet

Meters

Size 150

Size 175

Size 200

0-2000

0-610

150,000

121,500

105,000

175,000

141,750

122,500

200,000

162,000

140,000

2001-4500

611-1373

135,000

109,350

94,500

157,500

127,575

110,250

180,000

145,800

126,000

Feet

Meters

Size 225

Size 250

Size 300

0-2000

0-610

225,000

182,250

157,500

250,000

202,500

175,000

300,000

243,000

210,000

2001-4500

611-1373

202,500

164,025

141,750

225,000

182,250

157,500

270,000

218,700

189,000

Feet

Meters

Size 350

Size 400A

0-2000

0-610

350,000

283,500

245000

400,000

324,000

280,000

2001-4500

611-1373

315,000

255,150

220500

360,000

291,600

252,000

TABLE 3A - BTUH

Inputs and Capacities

by Altitude in the

UNTIED STATES for

Models PDH, SDH, RDH

TABLE 3B - BTUH

Inputs and Capacities

by Altitude in CANADA

for Models PDH, SDH,

RDH

Propane TO Natural Conversion Kit, P/N 212072

Applies to:

Models PDH, SDH, RDH Sizes 250 and 300

Equipped with one of the following valves:

Serial No. Code Description

Y5 or 1A

VR8305K4258, Single-stage, 3/4”

Y7 or 3A

VR8305N4289, Two-stage, 3/4”

Components:

Qty

P/N

Description

Use in Valve w/

Serial No. Code

1

98721 Spring Kit #394588 for VR8105, VR8205,

VR8305 Single-Stage Valves

Y5, 1A

1

197208 Spring Kit #396205 for VR8105, VR8205,

VR8305 Two-Stage Valves

Y7, 3A

1

208255 SIZE 250, Burner Orifice, L

1

221122 SIZE 300 - Burner Orifice, 8.0mm

1

64391 Conversion Tape

1

1401

Natural Gas Disk

1

197062 High Altitude Adjustment Label (use above 2000ft/610M)

Propane TO Natural Conversion Kit, P/N 212073

Applies to:

Models PDH, SDH, RDH Sizes 350 and 400A

Equipped with one of the following valves:

Serial No. Code Description

Y5 or 1A

VR8305K4258, Single-stage, 3/4”

Y7 or 3A

VR8305N4289, Two-stage, 3/4”

Components:

Qty

P/N

Description

Use in Valve w/

Serial No. Code

1

98721 Spring Kit #394588 for VR8105, VR8205,

VR8305 Single-Stage Valves

Y5, 1A

1

197208 Spring Kit #396205 for VR8105, VR8205,

VR8305 Two-Stage Valves

Y7, 3A

1

221123 SIZE 350 - Burner Orifice, 8.7mm

1

196897 SIZE 400A - Burner Orifice, 9.6mm

1

64391 Conversion Tape

1

1401

Natural Gas Disk

1

197062 High Altitude Adjustment Label (use above 2000ft/610M)

Propane to Natural Kits (cont’d) (Verify kit application.)