Table 1. Packaged Air Conditioner Blower Curves

Cooling Charging Charts

P6 Series Blower Curves

Model Number

External Static Pressure Drop - inches water column

P6SD-

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

High

1610

1562

1504

1442

1365

1295

1214

1109

X36

Medium

1367

1320

1271

1205

1138

1065

968

845

* Low

1153

1102

1043

990

912

831

731

618

High

2361

2278

2218

2141

2066

1976

1870

1758

X48

Medium

2026

1982

1935

1889

1822

1744

1660

1554

* Low

1584

1568

1532

1489

1445

1387

1322

1236

Tap T1

1515

1450

1380

1350

1280

1250

1200

1160

* * Tap T2

1580

1520

1460

1400

1300

1280

1260

1230

X60 * Tap T3

1740

1690

1650

1600

1360

1500

1460

1390

Tap T4

1960

1910

1840

1820

1540

1740

1700

1600

Tap T5

2090

2050

2010

1975

1780

1900

1850

1790

* Denotes factory set cooling speed

** Denotes factory set electric heating speed

NOTE: Airfl ow performance is with a dry coil

P6SD-X36 Charging Chart - Cooling

200

220

240

260

280

300

320

340

360

380

400

420

440

460

480

500

520

540

560

580

600

75

80

85

90

95

100

105

110

115

120

125

130

135

Liquid Temperature (F)

Liquid Pressure (psig)

Add refrigerant when below curve

Remove refrigerant when above curve

Figure 9: 13 SEER Cooling Charging Charts