Figure 3. Minimum Clearances

36"

36"

0"

36"

72"

rated performance See Figure 3 for minimum
clearances to obstructions.

Air Filter Requirements — Three phase units
“Only” are supplied from the factory with an
internal fi lter rack assembly. Air fi lters are not
supplied; a suitable air fi lter must be installed in
the unit or in the return air system for all units.
See Table 1 for internal fi lter size requirements.
When utilizing an Economizer or Fresh Air
Equipment, the factory installed filter rack
assembly must be removed prior to installation.
Refer to Table 1 for recommended fi lter sizes
when the factory installed fi lter system is not
used. Air fi lter pressure drop must not exceed

Conditioning Systems” (NFPA 90B), these
instructions and all applicable local codes.

NFPA publications are available by writing:

National Fire Protection Association

Batterymarch

Park

Quincy, Maine 02269


Unit Location — This air conditioner is
designed only for outdoor installations. Choosing
the location of the unit should be based on
minimizing the length of the supply and return
ducts. Consideration should also be given to
availability of electric power, service access,
noise, and shade. Sufficient clearance for
unobstructed airflow through the outdoor
coil must be maintained in order to achieve

Unit Size

Internal Filter Size

R6GD-X36

(2) 14” x 25” x 1”

or

(2) 14” x 25” x 2”

P6SD-X36

P6SD-X48

Q6SD-X36

P6SD-X60
Q6SD-X48/X60, R6GD-X48/X60

(2) 16” x 25” x 1”

or

(2) 16” x 25” x 2”

Figure 3a. Internal Filter Rack Location

Securing
Screw

Table 1. Internal Filter Size Requirements.