Reznor R6GP Unit Installation Manual User Manual
Page 30

30
R6GP-072(C/D)-100C
Factory Standard: 1Hp Horizontal Performance Chart
‡ Indicates Factory Sheave Setting for Pre-configured Units
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3 Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open
5
Turns
Open ‡
5.5
Turns
Open
6
Turns
Open
0.1
CFM
2999
2848
RPM
740
717
kW
0.86
0.76
0.2
CFM
2955
2785
2615
RPM
764
742
720
kW
0.88
0.79
0.69
0.3
CFM
2881
2738
2558
2377
RPM
792
766
745
723
kW
0.92
0.81
0.72
0.64
0.4
CFM
2812
2663
2514
2289
2085
RPM
821
795
769
745
727
kW
0.96
0.85
0.74
0.68
0.56
0.5
CFM
2729
2590
2426
2261
1995
1802
RPM
850
826
799
772
746
730
kW
0.97
0.85
0.77
0.68
0.60
0.46
0.6
CFM
2626
2462
2298
2026
1957
RPM
877
853
829
800
775
kW
0.99
0.87
0.76
0.64
0.58
0.7
CFM
2563
2349
2165
2018
RPM
903
879
855
833
kW
1.00
0.87
0.77
0.68
0.8
CFM
2545
2353
2100
1862
RPM
931
907
833
858
kW
1.02
0.91
0.78
0.68
0.9
CFM
2414
2306
2046
RPM
959
936
912
kW
1.04
0.92
0.79
1.0
CFM
2174
2013
RPM
964
941
kW
0.90
0.81
1.1
CFM
RPM
kW
1.2
CFM
RPM
kW
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
For operation at 208V: Deduct approximately 0.5% from Cfm
Table 6. R6GP-072C-100C Series - Horizontal Configuration