Reznor R6GP Unit Installation Manual User Manual
Page 32

32
Table 8. R6GP-072C-166C Series - Horizontal Configuration
R6GP-072(C/D)-166C
Factory Standard: 1Hp Horizontal Performance Chart
‡ Indicates Factory Sheave Setting for Pre-configured Units
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3
Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open
5
Turns
Open ‡
5.5
Turns
Open
6
Turns
Open
0.1
CFM
2914
RPM
724
kW
0.80
0.2
CFM
2703
RPM
728
kW
0.74
0.3
CFM
2771
2620
2469
RPM
778
755
731
kW
0.84
0.75
0.66
0.4
CFM
2879
2704
2529
2366
2203
RPM
833
807
781
757
732
kW
0.97
0.86
0.75
0.68
0.60
0.5
CFM
2655
2457
2259
2060
RPM
837
811
785
760
kW
0.89
0.78
0.67
0.59
0.6
CFM
2745
2569
2392
2169
1946
RPM
884
862
839
813
786
kW
1.02
0.89
0.77
0.69
0.60
0.7
CFM
2668
2474
2285
2095
RPM
912
888
865
842
kW
1.05
0.92
0.80
0.69
0.8
CFM
2572
2386
2200
1988
RPM
939
917
894
870
kW
1.07
0.93
0.79
0.70
0.9
CFM
2303
2097
RPM
942
920
kW
0.95
0.83
1.0
CFM
2254
2043
RPM
971
945
kW
0.96
0.85
1.1
CFM
RPM
kW
1.2
CFM
RPM
kW
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
For operation at 208V: Deduct approximately 0.5% from Cfm