Reznor R6GP Unit Installation Manual User Manual
Page 31

31
Table 7. R6GP-072C-166C Series - Downflow Configuration
R6GP-072(C/D)-166C
Factory Standard: 1Hp Downflow Performance Chart
‡ Indicates Factory Sheave Setting
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3
Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open
5
Turns
Open ‡
5.5
Turns
Open
6
Turns
Open
0.1
CFM
3025
2872
RPM
721
719
kW
0.88
0.80
0.2
CFM
2989
2832
2674
RPM
775
749
722
kW
0.92
0.83
0.74
0.3
CFM
2936
2788
2613
2437
RPM
802
776
751
725
kW
0.94
0.85
0.76
0.68
0.4
CFM
2879
2708
2537
2335
2132
RPM
831
804
777
753
728
kW
0.96
0.87
0.79
0.68
0.57
0.5
CFM
2826
2647
2437
2227
2016
RPM
857
834
808
782
756
kW
0.99
0.87
0.78
0.68
0.59
0.6
CFM
2769
2544
2318
2107
1895
RPM
881
860
838
811
784
kW
1.04
0.90
0.77
0.67
0.57
0.7
CFM
2625
2395
2220
2044
RPM
909
887
864
840
kW
1.01
0.86
0.78
0.70
0.8
CFM
2525
2323
2120
1920
RPM
937
915
892
868
kW
1.01
0.89
0.77
0.68
0.9
CFM
2449
2216
2004
RPM
964
941
919
kW
1.01
0.88
0.79
1.0
CFM
2160
1928
RPM
971
946
kW
0.92
0.81
1.1
CFM
RPM
kW
1.2
CFM
RPM
kW
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
For operation at 208V: Deduct approximately 0.5% from Cfm