2 supervised notification appliance wiring, 2 supervised notification appliance wiring -16 – SilentKnight 5104 Digital Alarm Communicator Transmitter 6 Zone User Manual
Page 23
Advertising

Installation
151053-L8
3-15
3.11.2 Supervised Notification Appliance Wiring
When using a supervised notification device any open or shorted wiring condition will be reported as a trouble.
Figure 3-10 illustrates how to wire a supervised notification device to the control panel. Refer to Section 6.2.7
Step 14 to program the notification circuit’s supervision properties.
Figure 3-10 Supervised Alarm Bell Wiring
Note: Polarities shown in Figure 3-10 illustrate the polarity in an alarm condition. Under normal conditions the
polarity of terminals 21 and 22 are reversed.
Model 7628
4.7 K
EOL
Wheelock
Model MB-G10-12-R
12 VDC Bell