SilentKnight 5104 Digital Alarm Communicator Transmitter 6 Zone User Manual
Page 26

Model 5104B Installation Manual
151053-L8
3-18
toward you. See Figure 3-13.
Figure 3-13 Rear Mounting Plate
3.
Set the desired ID for the 5230 by setting the dip switches (on = up) as follows:
*
Not supervised
4.
Pull wire through the wire access hole and connect the wires as follows:
5.
Snap the 5230 into place by lining up the 5230 onto the restraining tabs and snapping the 5230 into place.
Note: Refer to Section 5 for 5230 Operation.
ID Number
Dip Switch 1
Dip Switch 2
Dip Switch 3
Dip Switch 4
0*
On
On
On
On
1
Off
On
On
On
2
On
Off
On
On
3
Off
Off
On
On
130294
Quick Connect Cable
5230 Terminals
5104 Terminals
Number
Description
Number
Description
Brown
1
Annunciator Ground
23
Ground
Red
2
Annunciator Power
24
Accessory Power
Orange
3
Annunciator Input
25
Serial Data Out
Yellow
4
Annunciator Output
26
Serial Data In
Mounting Holes
Orientation Mark
Wire Access Hole
Restraining
Tabs
Restraining
Tabs