3 wiring requirements for slc device, 1 wiring slc in style 4 (class b) configuration, Wiring requirements for slc device -2 – SilentKnight SK-FFT User Manual

Page 30: 1 wiring slc in style 4 (class b) configuration -2

Advertising
background image

SK-FFT Installation and Operation Manual

4-2

54711

4.3 Wiring Requirements for SLC Device

The following information applies to the SK-Minimon - Mini Monitor module.

4.3.1

Wiring SLC in Style 4 (Class B) Configuration

No special wire is required for addressable loops. The wire can be untwisted,
unshielded, solid or stranded as long as it meets the National Electric Code 760-51
requirements for power limited fire protective signaling cables. Wire distances are
computed using copper wire.

Maximum wiring resistance is 40 ohms to the farthest SLC device.

Maximum loop length depends on the wire gauge.

Wire Gauge

Max. Distance

22 AWG

1200 feet

18 AWG

3100 feet

16 AWG

4900 feet

14 AWG

7900 feet

12 AWG

10,000 feet