Slant/Fin Gas Steam User Manual

Page 10

Advertising
background image

10

INSTALLATION AND PIPING RECOMMENDATIONS
When one or more steam boilers are replaced with a new

Caravan modular boiler system, there are certain conditions that

must be considered.

1.

All modules must be set on a level surface, and individually

leveled.

2.

When setting gas fired Caravan systems on a raised base, at

least 3 inches of the base must extend beyond the front and

sides of the bank of modules. This will ensure a smooth

pattern of combustion air entering the combustion chamber.

3. Leave a minimum of 7 inches between gas steam modules to

accommodate return piping, skimmer tapping, gauge glass

and low water cut off.

4. The module supply pipe must be increased from 2

1

2

" x 6" to

at least 3" (see figure 10, page 9). As shown, a 2

1

2

" x 6"

nipple is installed in the module supply tapping followed by

3" x 2

1

2

" reducing coupling and a 3" supply pipe. The 2

1

2

" x 6"

nipple is necessary to provide the needed clearances to

remove the pressure relief valve for servicing and

replacement. To minimize pressure drop, no more than

three 90 elbows should be installed between the module

supply tapping and the steam header (see figure 9, page 9).

5. All banks of modules must have an equalizer/drain line from

the supply header to the return header. This equalizer/drain

should be located at the end of the header that the system

steam supply is taken from. The equalizer/drain should be the

same size as the supply header (see figure 8, page 9). The

supply & return header for each bank should be sized

according to Table 8, page 9.

6. To prevent accumulation of condensate, steam headers

should be pitched down in the direction of steam flow and

toward the equalizer/drain with no reduction in size. Module

connections must be on the side of the header (horizontal) or

at any angle between the side and top of header, never

between the side and bottom. To prevent condensate in the

header from re-entering the boiler supply pipe, side connec-

tions must enter a header that is at least one size larger than

the boiler supply connections. Top or 45˚ top-angle connec-

tions are preferred and can enter a header of the same size

or larger. See Figure 9.The supply header for each module

should be sized according to Figure 10, page 9.

7. The supply connection between the building steam main and

the module steam header should be located between the last

boiler on the header and the equalizer/drain. Connection

must be at least 2 header diameters from the last module

(see Figure 8, Page 9).

8. Piping should provide a means for both surface and bottom

blow-down and flushing sediment from the system for clean,

safe and efficient operation (see Figures 11 and 12, Page 11

and Fig. 7 page 8).

9. The use of a pump control is recommended to regulate the

water level in a bank of boilers and prevent the bank from

operating with an unsafe low water condition. For protection

of banks with 2 to 5 modules, the control should be located

on the equalizer line. All applications require a low water

cut-off on each module and one cut off for each bank.

10. Supply and/or return shut-off valves on individual modules

are not recommended. However, if valves on individual

modules are unavoidable, additional safety controls are

required on each module. Full-port valves should be used to

minimize pressure drop and should be the same diameter as

the pipe.

11. Impurities and oxygen in fresh water cause scaling and leave

deposits in the boiler and surrounding pipes. This leads to

inefficient operation and other system problems. The older

the system, the greater the probable accumulation of scale.

Therefore, it is necessary to check the piping for blockage or

restriction and clean or replace the piping as required.

Applications such as process systems can result in excessive

introduction of fresh water into a steam boiler. This will dam-

age the boilers and void any warranty. Caravan modular

boiler systems are not recommended for applications

involving the use or discharge of raw steam or condensate.

In all cases, boiler water should be tested periodically to

determine if conditioning treatment is needed. Consult a

local boiler water treatment expert.

Advertising