Sequence of operation

When the building thermostat calls for heat, contacts (RC) of the
R8285B control closes. This energizes the coils of R1 and R2
relays. With these contacts closed all the modules are energized
to fire. This will bring the system pressure up quickly. The P404A
pressure controls on each module (not shown in diagram, see fig.

16) are set to the pressure required to heat the building. This will
stage the number of modules firing to meet the demands of the
building load. The required modules will continue to fire until the
thermostat is satisfied.

There are several manufacturers that provide more sophisticated
controls for modular steam systems.

MODULAR STEAM WITH SPACE TEMPERATURE CONTROL WIRING DIAGRAM

R

G

Y

W

C

MODULE 1

MODULE 2

BUILDING

THERMOSTAT

L4079B

MANUAL RESET

HI LIMIT PRESSURETROL

R8285B

TRANSFORMER/RELAY

PROVIDE OVERLOAD AND DISCONNECT

1

MEANS AS REQUIRED.

1

H

N

N

H

N

H

#42A LOW WATER

CUT-OFF & PUMP

1

2

5

6

4

CONTROL

120

VAC

CONTACTOR OR

BOILER FEED PUMP

STARTER FOR

FIELD SUPPLIED

TO SYSTEM

ALARM

DWG FILE #WIRING\0000051W

21-1/4"

22-3/4"

RESET

MANUAL

#67M LWCO

(IF REQUIRED)

MODULE 3

H

N

5 MODULES

MAXIMUM

ETC.

ETC.

RELAY

COIL (TYP)

120 VOLT

- FOR CONNECTIONS SEE WIRING AT

RC

R1

R2

MODULE ON PAGE NO. 16

AT MODULE ON

SEE WIRING

FOR CONNECTIONS

ON PAGE NO. 16

Figure 14: Space temperature control wiring diagram