Slant/Fin EC-10DV Series Venting User Manual

Eutectic, Ec-10dv series, Direct vent oil-fired water boiler/no. 2 oil

Advertising
background image

CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE

Basic Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Application

Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Vent Kit Description & Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Outside Terminal

Installing the outside terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

Connections to the outside terminal . . . . . . . . . . . . . . . . . . . . . . . . .5

Connections to appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Appliance adapter assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Joint assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Connection of vacuum relief valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

In addition to all the pertinent information regarding Natural
Draft Applications whenever a Mechanical Draft Application is
used it should be installed using the following instructions and
Figures 2 and 3 (on pages 4 and 5) as reference.

The terminating vent hood, and the inlet air hood are on
the same wall surface. and are on the wall opposite from
the prevailing wind wall.

All of the air for combustion to the burner is supplied
directly from the outside of the building or structure.

Not less than 305 mm (12 in.) above the total accumulated
snow and level grade.

Not less than 1219 mm (4 ft.) horizontally or below any
window, and door or air inlet and also not less than
305 mm (1 ft.) above any of these openings.

Not less than 914 mm (3 ft.) above a powered air inlet
device that is within 3048 mm (10 ft.).

Not less than 609 mm (2 ft.) from any other building.

At least 914 mm (3 ft.) from any inside corner of a building

At least 305 mm (1 ft.) from any roof soffit or ridge vent.

At least 2134 mm (7 ft.) above any public walkway.

All of the vent construction consists of approved materials,
and terminates at an approved stainless steel hood.

All of the vent piping must be sealed from air leaks.

The vent pipe bend radius is 305 mm (12 in.)

Brace metal strapping every 914 mm (36 in.) to support
vent pipe and prevent it from sagging.

Follow the national codes for the installation of oil burning
equipment in USA-NFPA 31, in Canada CAN/CSA - B139
and local regulations.

DIRECT VENT OIL-FIRED WATER BOILER/NO. 2 OIL

VENTING INSTALLATION INSTRUCTIONS

EUTECTIC

EC-10DV Series

PUBLICATION NO. ECDV40-V RevA

Printed in U.S.A. 1113

Part No. 470912000

Installation Considerations

DO NOT DESTROY

THESE INSTRUCTIONS MUST

REMAIN WITH EQUIPMENT

Slant/Fin EC-10DV SERIES, models DV are approved for installation

as a direct vent system. The following basic guidelines should be

observed according to the venting system in use. In addition, it is

strongly recommended that the applicable precautions for Natural

Draft Applications be used.